After a few seconds, the panel will automatically return
to Test Mode and the device LED will be turned off. The
panel is then ready to test the next device.
Note: Up to one minute must be allowed for smoke
sensors to clear.
If a fire alarm signal is received from a zone other than
those being tested, all sounder output and relay output
circuits will activate as configured for a zone in alarm. The
sounders will continue to ring until silenced from the panel.

4.9.4 Auto High Test - User Option

The Auto High Test, if configured during commissioning,
automatically polls and tests all devices on the loop at a
specified time of day. This operation takes about 70-80
seconds to complete. To run the test manually:
1 From the Test Menu, using the numeric keypad press
the '
[U0 Test]
1:LEDs
4:Auto High Test
2 When the LCD displays the start Auto High Test
message, press the '
Manually start automatic high test ?
Press
to confirm
3 Each sensor is tested individually. The device under
test is displayed on line 2 of the LCD in the format
shown below, then re-displays the Test Menu.
[Sensor nn in test]
4 After each device test the pass or fail message is
displayed, as in the examples below:
Sensor nn passed
[Sensor nn in test]
Sensor nn failed
[Sensor nn in test]
5 If a fault occurs while the Auto High Test is active the
LCD displays a fault message (example given below):
FAULT
DEVICE FAILED AUTO HIGH TEST
Press the '
device text information. Press the '
to the Test menu. Clear the fault and repeat the test.
24
' button to select the Auto High Test.
4
2:LCD
5:Outputs
' button to start the test.
5
Test started ! !
Total failed:nn
Total failed:nn
01 / 03 Z01 M12 MCP
' button to display additional zonal and
6
3:Zones
: More
<:Cancel
<:Cancel
<:Cancel
<:Cancel
14:55
>
' button to return
4