ID61/62 Series Panel - Operating Manual

4.1.4 Keyswitch

The panel is fitted with a keyswitch which provides an
alternative to the Level 2 access code. If the keyswitch is
in the enabled position, it overrides the requirement for a
Level 2 access code. Therefore, if an alarm condition
occurs the keyswitch enables the immediate operation
of the control keys.
With the keyswitch in the enabled position the Level 2
menus are accessible by pressing the '
[U0] 1:Test

4.2 MUTE BUZZER Pushbutton

Operating the MUTE BUZZER pushbutton when an alarm
or fault has occurred, silences the internal buzzer. If the
Primary Delay is active during an alarm condition this
pushbutton will also terminate this delay and start the
Extend Delay time.
The internal buzzer remains silent until the system is
RESET or the panel detects another alarm condition.

4.3 EXTEND DELAY Pushbutton

With the occurrence of an alarm and with the Primary
Delay active, pressing the EXTEND DELAY pushbutton
cancels the initial response time and initiates the fire
investigation period (refer to Section 3.1.1 Fire in
Delayed Mode). The DELAY ACTIVE LED remains
illuminated until the delay timer expires.