Disabled - User Option; Alarm Count - User Option - Honeywell NOTIFIER ID61 Operating Manual

Table of Contents

Advertisement

5
A
DISABLEMENT
< - - - Zone Text - - - >
DISABLEMENT
< - - - Zone Text - - - >
2
6
997-458-000-8, Issue 8
January 2010
ID61/62 Series Panel - Operating Manual

4.12.5 Disabled - User Option

The Disablement User Option allows the user to view all
current loop-based input disablements recorded on the
system. To view each disablement in turn, from the VIEW
Mode menu:
1 Using the numeric keypad, press the '
[U0 View] 1:Log
4:Input Events
2 The LCD automatically displays either:
DISABLEMENT
< - - - Zone Text - - - >
There are no loop devices disabled
3 If more than one disablement is present, press the
B
C
D
E
01 / 09 Z01 S02 TMP
< - - - Device Text - - - >
09 / 09 Z01 S07 TMP
< - - - Device Text - - - >
4 Press the '

4.12.6 Alarm Count - User Option

The Alarm Count User Option allows the user to view the
number of times the panel has entered alarm condition
since manufacture. To view the Alarm Count, from the
VIEW Mode menu:
1 Using the numeric keypad, press the '
[U0 View]
8: Voltages
Current Alarm Count is
2 The LCD displays the Alarm Count. Press the '
42
select the Disablements display.
2:Devices
5:Disabled
a. The zone disablements, or
01 / 01 Z01 S02 TMP
< - - - Device Text - - - >
b. The NO disablements message, if no current
Disablements are present on the system.
'
/
' buttons to scroll through the Disablement
2
8
entries (see examples below):
a. Condition,
F
G
b. Disablement currently
c. Active disablements,
8
d. Zone number,
e. Device address,
f. Device type,
g. Zonal and device text
' button to return to the View Mode
4
menu.
select the Alarm Count display.
6: Maint.
7: Alarm Count
9: Version
12
button to return to the View Mode menu.
' button to
5
3:Faults
: More
<:Exit
displayed,
(if any).
' button to
6
: More
<:Exit
'