997-458-000-8, Issue 8
January 2010
ID61/62 Series Panel - Operating Manual

4.9 TEST - User Option

The following tests are available at Access Level 2 from
the Test - User Option menu:
a. LEDs
b. LCD
c. Zones
d. Auto High Test
e. Outputs
f. Buzzer
g. Keyboard
To start the TEST - User Option:
1 At the 'Status: NORMAL' message, press the '
button. The LCD prompts for a Level 2/3 access code.
(To cancel, press '
ACCESS TO MENUS RESTRICTED
Enter Level 2/3 Passcode: . . . .
Note: Entering an incorrect access code causes the LCD
to display the 'ERROR - INCORRECT PASSCODE
! ! !' message, then an automatic return to the
access code prompt.
2 Either turn the keyswitch or, using the numeric keypad,
enter the correct Level 2 access code and confirm
using the '
displayed with the user number ([U0] to [U9]) in the
top left-hand corner.
[U0] 1 : Test
4 : View Mode
Note: Print menu option displayed only when a printer is
fitted.
Extinguishing System - Testing SLC device
outputs.
To prevent inadvertant operation of the direction and
release valves during testing, zones containing the
associated SLC devices MUST FIRST be put into
TEST mode. Also, where a zone test is manually
activated using an input module, extinguishant
bottles MUST FIRST be disconnected to prevent
unauthorized extinguishant discharge.
Note: A manual release reset will not stop the
extinguishant discharge because of a physical link
between the direction valve inputs and outputs.
20
').
4
' button. The User Option menu is
5
2 : Disable/Enable
3 : Clock
5 : Commission
'
< : BackSp
6: Print