4.5 SILENCE / RESOUND Pushbutton
The term 'silence' as used throughout this manual,
describes a temporary state the panel enters whenever
the SILENCE / RESOUND pushbutton is pressed to stop
the sounders operating. While the panel is in this state, a
new fire alarm, operating the SILENCE / RESOUND
pushbutton
END DELAY / EVACUATE pushbutton, will re-sound all
previously silenced sounders.
You can suspend all sounder output delays and silence
all sounder outputs which are operating as a result of a
FIRE alarm or an EVACUATE operation. Provided that
the pushbuttons have been enabled for Level 1 operation
and delays are active, proceed as follows:
1 Press the SILENCE / RESOUND pushbutton. The
following are not switched off by this operation:
a. The internal FIRE buzzer.
b. Any output modules configured in the CBE Rules
during commissioning NOT to be silenced by the
SILENCE/ RESOUND pushbutton.
2 To start the sounders again in the same pattern as
they were previously operating and reactivate any
programmed delays, press the SILENCE / RESOUND
pushbutton.
3 The panel may have been configured, during
commissioning, to illuminate the SOUNDERS
SILENCED LED when the SILENCE/RESOUND
pushbutton is pressed (non-default selection).
Pressing the SILENCE / RESOUND pushbutton again
to operate the sounders, the SOUNDERS SILENCED
LED extinguishes.
Note: If the pushbuttons are enabled to operate at
Level 2, enter the Level 2 passcode in the manner
described in the RESET pushbutton procedure
(Section 4.6).
16
again
or
operation
of
the