Fire In Delayed Mode - Honeywell NOTIFIER ID61 Operating Manual

Table of Contents

Advertisement

EN54-2: 7.11 (c)
Total time for configured
delays MUST NOT
exceed 600 seconds.
1a
1b
EXTEND DELAY
2
3
ID61/62 Series Panel - Operating Manual

3.1.1 Fire in Delayed Mode

The DeIayed Mode introduces a delay between an alarm
being detected and the sounders and output modules
activating. Depending upon the panel configuration, this
may be a single delay or a 2-stage delay (an initial brief
delay which may be extended by pressing EXTEND
DELAY to allow an investigation). The delay is initiated if
the panel enters an alarm condition during Delayed Mode.
Note: For any configured delays, pressing EXTEND
The delayed mode status is indicated on the LCD as below:
Status: DELAYED
1a When the panel enters a fire condition the delay
FIRE
MAIN BUILDING
FIRE
FIRE
DISABLEMENT
TEST
MAIN BUILDING
1b If the 2-stage delay is configured, pressing the
Note: If configured to do so, the DISABLEMENT LED is
2 If the delay time elapses, a full alarm condition is
Note: A Fire alarm in a different zone to the first alarm
3 When the cause of the alarm has been cleared, press
Status: NORMAL
7
DELAY cancels the initial response time and initiates
the fire investigation period. Activation of an MCP
will also cancel any configured delay period. The
maximum time for the primary initial response time
is 300 secs; the TOTAL time for both periods is
600 secs. The delay period can only be configured
at Level 3 by the Commissioning Engineer.
Sat 01/12/2001
countdown is started and the internal buzzer sounds.
The buzzer can be silenced by pressing the MUTE
BUZZER pushbutton. The LCD displays the alarm
information on the top line; this alternates for 1 sec
every 5 secs with the time remaining before the
shortest day mode delay expires.
02 / 05
Z01
S16
FIRST FLOOR ROOM 36
02 / 05
FIRST FLOOR ROOM 36
EXTEND DELAY pushbutton during the primary delay
initiates the fire investigation period.
illuminated (not default) from the initiation of the
primary delay and extinguishes at the end of the
primary delay period or fire investigation period.
entered (the configured fire outputs are activated). To
cancel the delay, operate the END DELAY/EVACUATE
pushbutton; the full alarm condition is entered and the
internal buzzer sounds (it can be silenced by pressing
the MUTE BUZZER pushbutton).
will also cancel the delay.
the RESET pushbutton to return to the 'Status:
NORMAL' message.
Sat 01/12/2001
00:00:00
ION
11:59
DELAYED: 050
00:00:00
997-458-000-8, Issue 8
January 2010