3-Phase Mains Connection 230/240 V; Connection Diagrams; Terminal Data - Lenze i550 Series Mounting Instructions

Protec ip31, ip66 / nema 1, nema 4x outdoor
Hide thumbs Also See for i550 Series:
Table of Contents

Advertisement

Available languages

Available languages

Electrical installation
Mains connection

3-phase mains connection 230/240 V

3-phase mains connection 230/240 V

Connection diagrams

The inverters I55AxxxxD do not have an integrated RFI filter in the AC mains supply.
In order to meet the EMC requirements according to EN 61800−3, an external EMC filter according
to IEC EN 60939 must be used.
The user must verify that the conformity with EN 61800−3 is fulfilled.
Mains connection
L2
3/N/ PE
L3
AC
208 V ... 240 V
N
PE
F1
...
F3
3/ PE
Q1
AC
170 V ... 264 V
45 Hz ... 65 Hz

Terminal data

Inverter
Connection
Connection type
Max. cable cross-section
Stripping length
Tightening torque
Tools required
Inverter
Connection
Connection type
Max. cable cross-section
Stripping length
Tightening torque
Tools required
84
L2
3/N/ PE
L3
AC
208 V ... 240 V
N
PE
F1
...
F3
3/ PE
Q1
AC
170 V ... 264 V
45 Hz ... 65 Hz
I55APxxxD
kW
0.37 ... 0.75
hp
0.5 ... 1.0
X100
Screw
terminal
mm²
4
AWG
10
mm
9
inch
0.35
Nm
0.5
Ib-in
4.4
0.6 x 3.5
I55APxxxC
kW
3.0 ... 5.5
hp
4.0 ... 7.5
X100
Screw
terminal
mm²
6
AWG
8
mm
9
inch
0.35
Nm
0.5
Ib-in
4.4
0.6 x 3.5
PE
X105
Screw
PE screw
terminal
6
4
10
10
10
9
0.4
0.35
2
0.5
18
4.4
Torx 20
0.6 x 3.5
PE
X105
Screw
PE screw
terminal
6
6
10
8
10
9
0.4
0.35
2
0.5
18
4.4
Torx 20
0.6 x 3.5
Motor connection
I55APxxxD
1.1 ... 2.2
1.5 ... 3.0
X100
PE
Screw
PE screw
terminal
6
6
10
10
9
10
0.35
0.4
0.5
2
4.4
18
0.6 x 3.5
Torx 20
I55APxxxC
7.5 ... 11
10 ... 15
X100
PE
Screw
PE screw
terminal
16
16
6
6
11
11
0.4
0.4
1.2
3.4
11
30
Phillips head
Screwdriver
screwdriver
0.8 x 4
PZ2
M
3~
X105
Screw
terminal
6
10
9
0.35
0.5
4.4
0.6 x 3.5
X105
Screw
terminal
16
6
11
0.4
1.2
11
Screwdriver
0.8 x 4

Advertisement