Electrical installation
Electrical installation
Important notes
DANGER!
Electrical voltage
Possible consequences: Death or severe injuries
▶ Any work on the inverter must only be carried out in the deenergised state.
▶ Inverter up to 45 kW: After switching off the mains voltage, wait for at least 3 min before you start
working.
▶ Inverter from 55 kW onwards: After switching off the mains voltage, wait for at least 10 min before you
start working.
DANGER!
Dangerous electrical voltage
The leakage current against earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences: Death or severe injuries when touching the device in the event of an error.
▶ Implement the measures requested in EN 61800−5−1 or EN 60204−1. Especially:
▶ Fixed installation
▶ The PE connection must comply with the standards (PE conductor diameter ≥ 10 mm
conductor)
76
2
or use a double PE