MAINTENANCE CONT.
BATTERY REPLACEMENT
Step 1: Remove the front panels.
Step 2: Remove the retaining screws from the battery retention cover and then remove the cover itself.
Step 3: Pull the battery trays out slowly and then put the new battery trays into the compartment.
1
2
3
Step 4: Insert the battery connectors and tighten the screws of battery retention cover.
Step 5: Install the front panels. Execute a battery test via the LCD control panel, go to the Configuration
Menu, then scroll to the UPS Diagnostic then select battery test and Activate, then scroll to Reset
ReplaceBAT to reset the battery replacement date. This operation can also be done via PowerPanel®
Business Edition Agent or RMCARD web interface. Please see their respective User Manuals for
detailed instructions.
4
5
30