HARDWARE INSTALLATION CONT.
RACKMOUNT INSTALLATION: RACKMOUNT EARS INSTALLATION CONT.
5
3
4
Rackmount ear
Rackmount rail
Step 5: Place and secure the UPS on the rails
Slide the hanging brackets on the UPS on to the rails mounted in the rack with the front of the unit facing
toward you. Secure the UPS to your rack with four black M5X12L pan head screws at the front of the rack
(square holes 5 and 7 as shown above).
Once completed, perform the same steps for the Battery module. Remove the internal battery trays from
the Battery module before installing it. (See Battery Replacement section) The Battery module must be
installed below the Power module. Place the internal battery trays back into the Battery module after
installation. (See Battery Replacement section)
NOTE: To slide the UPS out from the rack
The UPS will be secured by a safety locking mechanism midway of pulling it out of the rack. Use both hands
to hold the UPS and press the safety locking tab to pull the UPS out.