Replacing The Battery; Battery Replacement Procedure - CyberPower CST150XLU User Manual

Hide thumbs Also See for CST150XLU:
Table of Contents

Advertisement

REPLACING THE BATTERY

Replacement of batteries located
in an OPERATOR ACCESS AREA
1. When replacing batteries, replace with
the same number of the following
battery: CyberPower / RB1290X2 for the
CST150XLU
2. CAUTION! Risk of Energy Hazard, 24 V,
maximum 9 Ampere-hour battery. Before
replacing batteries, remove conductive
jewelry such as chains, wrist watches, and
rings. High energy conducted through
these materials could cause severe burns.
3. CAUTION! Do not dispose of batteries in a
fre. The batteries may explode
Yellow Wire to (+) Red Connector
Black Wire to (-) Black Connector

BATTERY REPLACEMENT PROCEDURE

1.
Turn of and unplug all connected equipment.
2. Turn the UPS of and unplug it from the AC power source.
3. Turn the UPS on its side.
4. Remove two retaining screws located on the bottom of the UPS.
5. Slide the battery compartment cover completely of of the unit.
6. Remove the battery which is located on the right side from the compartment.
7. Disconnect the battery wires from the right side of the battery.
8. Slide the remaining battery from left to right and remove it from the compartment.
9. Disconnect the battery wires from the remaining battery.
10. Install the "left side" replacement battery by connecting the yellow wire (+) to the red
connector from the battery and the black wire (-) to the black connector from the battery.
Place the battery into the left side of the compartment.
11. Install the "right side" replacement battery by connecting the red wire (+) to the red
connector from the battery and yellow wire (-) to the black connector from the battery.
Place the battery into the right side of the compartment. Note: Only new batteries should
be used for replacement and both batteries should be replaced at the same time to insure
maximum life span.
12. Slide back the battery compartment cover and tighten the retaining screws.
13. Recharge the UPS for 8 to 16 hours to fully charge the battery.
REMINDER: Batteries are considered HAZARDOUS WASTE and must be disposed of properly. Most retailers that sell lead-acid
batteries collect used batteries for recycling, as required by local regulations.
4. CAUTION! Do not open or mutilate
batteries. Released material is harmful to
the skin and eyes. It may be toxic.
5. CAUTION: A battery can present a risk
of electrical shock and high short circuit
current. The following precautions should
be observed when working on batteries:
1) Remove watches rings, or other
metal objects.
2) Use tools with insulated handles.
CAUTION - RISK OF EXPLOSION IF BATTERY
IS REPLACED BY AN INCORRECT TYPE.
DISPOSE OF USED BATTERIES ACCORDING
TO LOCAL REGULATIONS
Red Wire to (+) Red Connector
Yellow Wire to (-) Black Connector

Advertisement