USING THE UPS SYSTEM CONT.
LCD Configuration Settings Cont.
CONFIGURE
SUBMENU
Language
Generator Mode
2
Communication
Dry Relay Set
Converter Mode
3
Screen Saver
Clear Event Log
Button OFF LOCK
Charger Function
AVAILABLE SETTINGS
[English] [Español-Spanish] [Français-French]
[Deutsch-German]
User can select the desired LCD control panel language.
[Disable] [Enable]
When the UPS input power source is a generator set
the UPS will operate normally without transferring to
Battery Mode when set to [Enable].
[Disable] [Enable]
All communication ports on the UPS are
[Disable] or [Enable].
[I/P Power Fail] [Battery Low] [Summary Alarm]
[UPS On Bypass] [UPS Fail]
Select what UPS events will trigger real potential-free
dry contacts for industrial control.
[Converter O ] [O/P Freq = 50Hz] [O/P Freq = 60Hz]
Sets [O/P Freq = 50Hz] or [O/P Freq = 60Hz]
to convert the input frequency to the required
output frequency.
[Disable] [1 Minutes] [5 Minutes]
Sets the amount of time the LCD screen stays on
after no user input. The [Disable] option keeps the
LCD screen on at all times.
[Activate?]
Clears all the events stored in the LCD control panel
Event Log.
[Disable] [Enable]
To prevent accidental UPS power ON/OFF button
operation set to [Enable]. The Power ON/OFF button
will be locked and will not function.
[SBM] [Constant]
Set [SBM] to activate Smart Battery Management
to charge the batteries.
Set [Constant] to use trickle charge method to
charge the batteries.
DEFAULT SETTING
English
Disable
Enable
I/P Power Fail
Converter OFF
5 minutes
None
Disable
SBM
26