ELECTRICAL INSTALLATION CONT.
WITHOUT BACKFEED PROTECTION CONFIGURATION
1.
Hardwire the input terminals as shown in the following diagram.
2. Do not remove the interconnection wires (Jumper1 / Jumper2) on "Backfeed Protection Connector".
Mains
L1 L2 PE
WITH BACKFEED PROTECTION CONFIGURATION
1.
Connect a user supplied external isolation device (Magnetic Contactor) upstream and outside the UPS
and capable of supporting the UPS input current.
2. Remove the interconnection wires (Jumper1 / Jumper2) on "Backfeed Protection Connector".
3. Hardwire the input terminals and "Backfeed Protection Connector" as shown in the following diagram.
4. The external isolation device must be installed in the Mains path.