CyberPower OL6KRT Installation And Operation Manual page 31

Smart app online ups system
Hide thumbs Also See for OL6KRT:
Table of Contents

Advertisement

USING THE UPS SYSTEM CONT.
LCD Configuration Settings Cont.
CONFIGURE
SUBMENU
ECO Mode
1
Manual Bypass
UPS Diagnostic
Audible Alarms
EBM Number
Wiring Fault
NCL Control
AVAILABLE SETTINGS
[Disable] [Enable]
[V Range= +/-15%] [V Range= +/-10%] (for [Enable])
When ECO mode is enabled the UPS will check the
following bypass quality specifications
(1)
Bypass voltage is inside the [V Range= +/-10%]
(default setting) or [V Range= +/-15%]
(2)
Bypass frequency is inside the +/-3 Hz range of
output nominal frequency
[Disable] [Enable]
When performing UPS maintenance, the user can
manually transfer the connected load to bypass
without interrupting the supply of power.
[Battery Test] [Alarm Test] [Indicator Test] [Fan Test]
[Activate?]
Starts a manual battery test. The UPS will operate 10
seconds on Battery Mode to check battery condition.
Starts a manual alarm test. The buzzer will sound
for 5 seconds.
Starts a manual indicator test. The UPS will turn on all
LEDs and light the LCD background for 5 seconds.
Starts a manual fan test. The UPS will operate fans at
full speed for 5 seconds.
[Disable] [Enable] [Only Battery Low]
User can [Disable] or [Enable] the audible alarm and
can also set [Only Battery Low] to alarm only when
the battery is low in Battery Mode.
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
Set the number of EBM (Extended Battery Modules)
to get the correct estimated runtime.
[Disable] [Enable]
Set [Disable] or [Enable] to automatically check
for an input wiring fault.
[Outlet On] [Outlet O ]
Set Noncritical Load (NCL) [Outlet On] or [Outlet
O ]. When NCL is set to [Outlet O ], the NCL
output power will turn o immediately.
DEFAULT SETTING
Disable
V Range= +/-10%
Disable
[Battery Test]
None
Enable
0
Disable
Outlet On
25