CyberPower OL6KRT Installation And Operation Manual page 30

Smart app online ups system
Hide thumbs Also See for OL6KRT:
Table of Contents

Advertisement

USING THE UPS SYSTEM CONT.
LCD Configuration Settings Cont.
8. Press the "ENTER" button to select the parameter you want to change.
9. You may be prompted to save the selection, if so press the "ENTER" button to save the setting. Some
options are saved and started automatically. (See the following table for additional details.)
10. Press the "ESC" button to cancel or return to the previous screen.
CONFIGURE
SUBMENU
Output Voltage
Sync Freq Window
Bypass V Window
Bypass Condition
AVAILABLE SETTINGS
= [200V] [208V] [220V] [230V] [240V]
Sets the UPS output voltage
Range= [+/- 1%] [+/- 2%] [+/- 3%] [+/- 4%] [+/- 5%]
[+/- 6%] [+/- 7%] [+/- 8%] [+/- 9%] [+/-10%]
Sets the output synchronization frequency range
If input line frequency is outside this range, the UPS
will lock in at the nominal frequency
Range= [+10%/-10%] [+10%/-15%] [+10%/-20%]
[+15%/-10%] [+15%/-15%] [+15%/-20%]
Sets Bypass Voltage range
[Check Freq/Volt] [Check Volt Only] [No Bypass]
Bypass Condition :
The default setting [Check Freq/Volt] means the UPS
will check the specifications (1) and (2) when the UPS
has a fault and needs to transfer to Bypass.
The setting [Check Volt Only] means the UPS will
check the following specification (1) when the UPS has
a fault and needs to transfer to Bypass.
(1) Bypass voltage is inside the range of
"Bypass V Window".
(2) Bypass frequency is inside the range of
"Sync Freq Range".
The setting [No Bypass] means the UPS is forbidden
to transfer to Bypass when UPS has a fault.
DEFAULT SETTING
208V
+/- 5%
+10%/-15%
Check Freq/Volt
24

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ol8krtOl10krt

Table of Contents