HARDWARE INSTALLATION

CyberPower UPS systems can be installed in a rackmount or vertical/tower orientation. This versatility
is especially important to growing organizations with changing needs that value having the option to
position a UPS on the floor or in a rackmount system. Note that the included rack mounting hardware is
only compatible with square hole racks. Please follow the instructions below for the respective mounting
methods.

RACKMOUNT INSTALLATION

Caution: Important Instructions
To prevent the risk of fire or electric shock, only use the supplied hardware to attach the mounting brackets.
Step 1: Remove the dust covers
Remove ten dust covers from the screw holes as shown below.
Step 2: Rackmount ear & hanging bracket installation
Attach two rackmount ears to the UPS using eight black M5X7L flat head screws and tighten two hanging
brackets using six silver M5X6L pan head screws.
1
2
Step 3: Rackmount rail Installation
The mounting depth of the included rackmount rails can adjust from 20.5 in to 36 in (52 cm to 91.5 cm).
Select the proper holes in the rack for positioning the UPS in the rack. The UPS takes up 3 rack units: rack
hole positions 1 through 9.
Position the guide screws on the back of the rackmount rails into the rear rack square holes to temporarily
support the rails in place.
Step 4: Adjust rackmount rails to fit your rack
Adjust the rail depth to match your rack depth. Attach each rackmount rail to your rack with two black
M5X6L pan head screws and two plastic washers at the front of the rack (square holes 4 and 8 as shown
below). Secure each rail to the rear of the rack with two black M5X6L pan head screws and two plastic
washers.