USING THE UPS SYSTEM CONT.
LCD Configuration Settings Cont.
CONFIGURE
SUBMENU
Signal Inputs
Charger Check
With Transformer
Backfeed Check
Reset ReplaceBAT
IP Address
Reset Load Energy
LowBat Capacity
4
LowBat Runtime
4
Period Battery Test
This function can't be set when Manual Bypass, Generator Mode or Converter Mode is enabled.
1
UPS has no bypass when Generator Mode is enabled.
2
UPS has no bypass when Converter Mode is enabled. This function can only be set before the UPS is on.
3
The Low Battery threshold setting will only a ect the warning of Power Management Software (PowerPanel® Business) and RMCARD interface.
4
If function is disabled, the Smart Battery Management (SBM) carries out battery tests when certain operating conditions are met.
5
Silencing Audible Alarms
1.
Press any of the four function buttons on the LCD control panel.
Note:
audible alarm.
2. Change the "Audible Alarms" option to "Disable" in the LCD control panel and it will no longer give an
audible alarm for any malfunction.
[Disable] [EPO] [ROO][Manual Bypass]
Set [EPO] (Emergency Power O ) to shut down the UPS remotely
when the contact is open.
Set [ROO] (Remote On/O ) to turn the UPS on remotely when
the contact is closed and turn the UPS o remotely
when the contact is open. The On/O power button on the front
panel will be disabled when set to [ROO].
Set [Manual Bypass] to use Maintenance Bypass PDU (MBP).
Please refer to the MBP user manual for correct operating procedures.
If you don't have install MBP , please don't set Signal Inputs to
[Manual Bypass].
[Disable] [Enable]
Set [Disable] or [Enable] to constantly monitor the charger function.
[Disable] [Enable]
Set [Enable] when UPS is installed with a step-down transformer.
[Disable] [Enable]
Set [Enable] to activate backfeed connector function.
[Activate?]
Manually reset the Battery Replacement date.
[Mode:DHCP] [Mode:Manual]
[IP Address] [Subnet Mask] [Gateway] (for [Mode:Manual])
Select [Mode:Manual] to set [IP Address] [Subnet Mask]
[Gateway] on the network card (RMCARD) or select DHCP to
retrieve IP address settings from the local network DHCP server.
[Activate?]
Reset Load Energy Consumption (KWH) value.
Threshold= [20%][25%] [30%][35%]......[55%][60%][65%]
Threshold= [0min][1min][2min][3min]......[29min][30min]
[Disable
][1 Weeks][2 Weeks] [3 Weeks] [4 Weeks]
5
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
AVAILABLE SETTINGS
Battery Low" condition. This condition will still result in an
DEFAULT SETTING
Disable
Disable
Disable
Disable
None
Mode:DHCP
None
None
20%
5min
Disable
27