Goodrive100-PV Series Solar Pumping VFD
Function
code
sudden power
P11.02
decrease ratio at
sudden power loss
P15 Group
Special functions for PV inverters
P15.00
Vmpp voltage
P15.01
Name
Detailed illustration of parameters
loss
Setting range: 0.00Hz–P00.03/s
After the power loss of the grid, the bus
voltage drops to the sudden frequency
decrease point, the VFD begin to
decrease the running frequency at
P11.02, to make the VFD generate
Frequency
power again. The returning power can
maintain the bus voltage to ensure a
rated running of the VFD until the
recovery of power.
0: Invalid
1: Enable
PV inverter
0 means the function is invalid and the
selection
group of parameters cannot be used
1 means the function is enabled, and
P15 parameters can be adjusted
0: Voltage reference
1: Max. power tracking
0 means to apply voltage reference
reference
mode. The reference is a fixed value
and given by P15.02.
1 means to apply the reference voltage
Voltage
220V
degree
Frequency
decrease
260V
point
42
Function parameters
Default Modify
0.00Hz/s
400V
460V
1
1
○
◎
◎