The UPS runs in six basic operation modes, which are On-Line mode, Battery mode,
Bypass mode, Manual Bypass mode, ECO mode and Frequency Conversion mode.
NOTE:
1. In this user manual, Q1, Q2, Q3, Q4 and Q5 represents the following.
2. To enable the following operation modes, please refer to 6. UPS Operation &
7. LCD Display & Settings.
3.1
On-Line Mode
In On-Line mode, the main AC source supplies AC power via the Input Switch (Q1) to the
rectifier, and the rectifier converts the AC power to DC power and supplies the DC power to
the inverter. In the meantime, the rectifier provides charging power to the batteries. After
receiving the DC power, the inverter converts it into clean and stable AC power to the
connected critical loads via the Output Switch (Q4). During On-Line mode, the UPS's tri-
color LED illuminates green and the text 'On-Line' appears in the upper right corner of the
LCD screen.
Ultron DPS Series
Chapter 3 : Operation Modes
Code
Q1
Input Switch
Q2
Bypass Switch
Q3
Manual Bypass Switch
Q4
Output Switch
Q5
External Battery Cabinet's Breaker
Meaning
28