5.5

External Battery Cabinet Connection Warnings

NOTE:
The information of the battery parameters in this chapter may not be applicable to
the lithium-ion batteries. For relevant information, please refer to the manual of the
lithium-ion batteries. Whether you use the lead-acid batteries or the lithium-ion
batteries, please contact Delta service personnel for any battery/ battery cabinet's
setup and configurations.
You should connect the UPS with at least one external battery cabinet to ensure that the
connected critical loads are protected when a power failure occurs. You can connect up to
four units of external battery cabinets to the UPS.
• To ensure that the batteries are fully charged, please charge for at least 8 hours before
the initial use of the UPS. This guarantees that the UPS can provide sufficient backup
power to the critical loads when a power failure occurs. The charging procedures are as
follows.
(1) Connect the main AC source and the external battery cabinet(s) to the UPS. Please
refer to 5.4 Wiring.
(2) Follow 6. UPS Operation to turn on the UPS and the external battery cabinet(s).
After that, the unit will automatically charge the batteries.
• To connect the external battery cabinet(s) to the UPS, please refer to 5.4 Wiring and
Figure 5-47.
• For the external battery cabinet's grounding information, please refer to Figure 5-20 and
Figure 5-45.
Battery Parameters
UPS Rating
No.
1
Charge Voltage
2
Charge Current
3
Low Battery Shutdown Voltage
4
Battery Quantity
• The charge current is adjustable from 10A to the maximum. Each adjustment level is 1A.
Item
Float charge voltage: ± 272Vdc (default)
Equalized charge voltage: ± 280Vdc (default)
Default: ± 10A
± 210Vdc (default)
12V × 40 PCS (default)
300kVA
400kVA
Description
± 90A
± 120A
(Max.)
(Max.)
89
500kVA
600kVA
± 150A
± 180A
(Max.)
(Max.)

Hide quick links: