6.2.3
Bypass Mode Start-up Procedures
WARNING:
Before turning on the UPS, please read 6.1 Pre Start-up & Pre Turn-off Warnings
thoroughly and ensure that the precautions and instructions have been followed.
Step 1
Ensure that the Manual Bypass Switch (Q3) is in the OFF position.
Step 2
Switch ON the Output Switch (Q4).
Step 3
Switch ON the Bypass Switch (Q2).
Step 4
Now, the UPS runs in Bypass mode, the LCD screen shows as below, and the tri-color LED
indicator illuminates yellow.
Ultron DPS Series
104