7.5.3 Precautions when charging refrigerant

7.5.4 To determine the complete recharge amount

7.5.5 To fix the fluorinated greenhouse gases label

ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
4P596806-1 – 2019.10
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
WARNING
Do NOT pierce or burn refrigerant cycle parts.
Do NOT use cleaning materials or means to accelerate the defrosting process
other than those recommended by the manufacturer.
Be aware that the refrigerant inside the system is odourless.
WARNING
The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If the
refrigerant leaks in the room and comes in contact with fire from a burner, a heater,
or a cooker, this may result in fire, or the formation of a harmful gas.
Turn off any combustible heating devices, ventilate the room, and contact the dealer
where you purchased the unit.
Do NOT use the unit until a service person confirms that the part from which the
refrigerant leaked has been repaired.
INFORMATION
Also read the precautions and requirements in the following chapters:
"1 General safety
"7.1 Preparing refrigerant
INFORMATION
If a complete recharge is necessary, the total refrigerant charge is equal to the
factory refrigerant charge (see unit name plate).
1 Fill in the label as follows:
Contains fluorinated greenhouse gases
RXXX
f
GWP: XXX
2
1
+
1
GWP × kg
1000
a
If a multilingual fluorinated greenhouse gases label is delivered with the unit (see accessories), peel off the
applicable language and stick it on top of a.
b
Factory refrigerant charge: see unit name plate
c
Additional refrigerant amount charged
d
Total refrigerant charge
e
Quantity of fluorinated greenhouse gases of the total refrigerant charge expressed as tonnes CO
equivalent.
f
GWP = Global warming potential
4
precautions" [
 6]
piping" [
4
 64]
a
kg
b
1
=
kg
c
=
2
d
kg
2
=
=
e
tCO
eq
2
7
Piping installation
|
2
Installer reference guide
81