Daikin Altherma 3 R F Installer's Reference Manual page 198

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

2/7
Field settings table
Breadcrumb
Field code
Setting name
User settings
└─ Preset values
└─ Room temperature
7.4.1.1
Comfort (heating)
7.4.1.2
Eco (heating)
7.4.1.3
Comfort (cooling)
7.4.1.4
Eco (cooling)
└─ LWT main
7.4.2.1
[8-09]
Comfort (heating)
7.4.2.2
[8-0A]
Eco (heating)
7.4.2.3
[8-07]
Comfort (cooling)
7.4.2.4
[8-08]
Eco (cooling)
└─ Tank temperature
7.4.3.1
[6-0A]
Storage comfort
7.4.3.2
[6-0B]
Storage eco
7.4.3.3
[6-0C]
Reheat
└─ Quiet level
7.4.4
└─ Set weather dependent
└─ Main
└────────────────── Set weather-dependent heating
7.7.1.1
[1-00]
Set weather-dependent heating
7.7.1.1
[1-01]
Set weather-dependent heating
7.7.1.1
[1-02]
Set weather-dependent heating
7.7.1.1
[1-03]
Set weather-dependent heating
└────────────────── Set weather-dependent Cooling
7.7.1.2
[1-06]
Set weather-dependent Cooling
7.7.1.2
[1-07]
Set weather-dependent Cooling
7.7.1.2
[1-08]
Set weather-dependent Cooling
7.7.1.2
[1-09]
Set weather-dependent Cooling
└─ Additional
└────────────────── Set weather-dependent heating
7.7.2.1
[0-03]
Set weather-dependent heating
7.7.2.1
[0-02]
Set weather-dependent heating
7.7.2.1
[0-01]
Set weather-dependent heating
7.7.2.1
[0-00]
Set weather-dependent heating
└────────────────── Set weather-dependent Cooling
7.7.2.2
[0-07]
Set weather-dependent Cooling
7.7.2.2
[0-06]
Set weather-dependent Cooling
7.7.2.2
[0-05]
Set weather-dependent Cooling
7.7.2.2
[0-04]
Set weather-dependent Cooling
Installer settings
└─ System layout
└─ Standard
A.2.1.1
[E-00]
Unit type
A.2.1.2
[E-01]
Compressor type
A.2.1.3
[E-02]
Indoor software type
A.2.1.7
[C-07]
Unit control method
A.2.1.9
[F-0D]
Pump operation mode
A.2.1.A
[E-04]
Power saving possible
A.2.1.B
User interface location
└─ Options
A.2.2.1
[E-05]
DHW operation
A.2.2.3
[E-07]
DHW tank type
A.2.2.4
[C-05]
Thermostat Type
A.2.2.A
[D-02]
Which type of DHW pump is installed?
A.2.2.B
[C-08]
External sensor
4P596814-1 - 2019.10
Low ambient temp. for LWT main zone heating
WD curve.
High ambient temp. for LWT main zone heating
WD curve.
Leaving water value for low ambient temp. for
LWT main zone heating WD curve.
Leaving water value for high ambient temp. for
LWT main zone heating WD curve.
'Low ambient temp. for LWT main zone cooling
WD curve.
High ambient temp. for LWT main zone cooling
WD curve.
'Leaving water value for low ambient temp. for
LWT main zone cooling WD curve.
'Leaving water value for high ambient temp. for
LWT main zone cooling WD curve.
Low ambient temp. for LWT add zone heating
WD curve.
High ambient temp. for LWT add zone heating
WD curve.
Leaving water value for low ambient temp. for
LWT add zone heating WD curve.
Leaving water value for high ambient temp. for
LWT add zone heating WD curve.
Low ambient temp. for LWT add zone cooling
WD curve.
High ambient temp. for LWT add zone cooling
WD curve.
Leaving water value for low ambient temp. for
LWT add zone cooling WD curve.
Leaving water value for high ambient temp. for
LWT add zone cooling WD curve.
Range, step
Default value
R/W
[3-07]~[3-06], step: A.3.2.4
22°C
R/W
[3-07]~[3-06], step: A.3.2.4
18°C
R/W
[3-09]~[3-08], step: A.3.2.4
24°C
R/W
[3-09]~[3-08], step: A.3.2.4
28°C
R/W
[9-01]~[9-00], step: 1°C
35°C
R/W
[9-01]~[9-00], step: 1°C
33°C
R/W
[9-03]~[9-02], step: 1°C
18°C
R/W
[9-03]~[9-02], step: 1°C
20°C
R/W
30~[6-0E]°C, step: 1°C
60°C
R/W
30~min(50, [6-0E])°C, step: 1°C
50°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
1: Level 1
2: Level 2
3: Level 3
R/W
-40~5°C, step: 1°C
-10°C
R/W
10~25°C, step: 1°C
15°C
R/W
[9-01]~[9-00], step: 1°C
35°C
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
R/W
10~25°C, step: 1°C
20°C
R/W
25~43°C, step: 1°C
35°C
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
R/W
[9-03]~[9-02]°C, step: 1°C
18°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
10~25°C, step: 1°C
15°C
R/W
[9-05]~[9-06]°C, step: 1°C
50°C
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
R/W
10~25°C, step: 1°C
20°C
R/W
25~43°C, step: 1°C
35°C
R/W
[9-07]~[9-08]°C, step: 1°C
12°C
R/W
[9-07]~[9-08]°C, step: 1°C
8°C
R/O
0~5
0: LT split
R/O
0
R/W (*1)
0: Reversible (*1)
R/O (*2)
1: Heating only (*2)
R/W
0: LWT control
1: Ext RT control
2: RT control
R/W
0: Continuous
1: Sample
2: Request
R/O
1: Yes
R/W
0: At unit
1: In room
R/O
0~1
1. Yes
R/O
0~6
1: Integrated
R/W
0: -
1: 1 contact
2: 2 contacts
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
R/W
0: No
1: Outdoor sensor
2: Room sensor
(*1) EHFH03S18DJ3V + EKHVCONV3_
Installer setting at variance with
default value
Date
Value
(*2) EHFH03S18DJ3V

Advertisement

Table of Contents
loading

Table of Contents