When the room thermostat requests heating, the indoor unit or the auxiliary
boiler starts operating depending on the outdoor temperature (status of the
changeover to external heat source). When the permission is given to the
auxiliary boiler, the space heating by the indoor unit is turned OFF.
Bivalent operation is only possible for space heating, NOT for domestic hot water
production. Domestic hot water is always produced by the DHW tank connected
to the indoor unit.
INFORMATION
During heating operation of the heat pump, the heat pump operates to achieve
the desired temperature set via the user interface. When weather-dependent
operation is active, the water temperature is determined automatically
depending on the outdoor temperature.
During heating operation of the auxiliary boiler, the auxiliary boiler operates to
achieve the desired water temperature set via the auxiliary boiler controller.
Setup
Integrate the auxiliary boiler as follows:
A
Main leaving water temperature zone
B
One single room
a
User interface used as room thermostat
b
Non-return valve (field supply)
c
Shut-off valve (field supply)
d
Auxiliary boiler (field supply)
e
Aquastat valve (field supply)
NOTICE
Make sure the auxiliary boiler and its integration in the system complies with
applicable legislation.
Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler
system.
Make sure the return water to the heat pump does NOT exceed 60°C. To do so:
-
Set the desired water temperature via the auxiliary boiler controller to
maximum 60°C.
-
Install an aquastat valve in the return water flow of the heat  pump. Set the
aquastat valve to close above 60°C and to open below 60°C.
Install non-return valves.
Make sure to only have one expansion vessel in the water circuit. An expansion
vessel is already pre-mounted in the indoor unit.
B
b
b
c
d
c
A
e
a
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
4P596806-1 – 2019.10