9
|
Configuration
Installer reference guide
122
#
[7.7.2.2]
[0-04]
[0-05]
[0-06]
[0-07]
(a)
Also see
"9.3 Weather-dependent
Leaving water temperature: Delta T source
The Delta T is the required temperature difference between entering and leaving
water. This applies to both temperature zones. Change the value of Delta T if
another minimum temperature difference is required for the good operation of the
heat emitters in heating or cooling mode.
#
[A.3.1.3.1]
[1-0B]
[A.3.1.3.2]
[1-0D]
Leaving water temperature: Modulation
To allow better matching of the heat  pump capacity with the actual required
capacity, enable the leaving water temperature modulation. If modulation is
enabled, the unit calculates the leaving water temperature according to the
difference between desired and actual room temperature. As a result, the
heat pump will have less start/stop cycles and thus operate more economical.
If modulation is enabled, you can also set the maximum modulation of the leaving
water temperature. The maximum modulation is the value by which the desired
leaving water temperature is increased or lowered.
#
[A.3.1.1.5]
[8-05]
N/A
[8-06]
Code
If you selected weather-dependent curve as a
setpoint mode, adjust the curve to your needs.
(a)
Set weather-dependent cooling:
T t
[0-05]
[0-04]
[0-07]
T
:
Target
t
(additional)
T
: Outdoor temperature
a
curve" [
Code
Delta T for heating
Range: 3°C~10°C
Delta T for cooling
Range: 3°C~10°C
Code
Modulated LWT:
0 (No): Disabled
1 (Yes): Enabled
Maximum modulation:
Range: 0°C~10°C
Description
[0-06]
T a
leaving
water
temperature
4
 124].
Description
Description
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
4P596806-1 – 2019.10