Reference Manual
May 2019
Appendix A
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 87
Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 87
Performance specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 95
Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 96
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 97

A.1 Specifications

The following specifications are for the Rosemount 8600D
except where noted.

A.2 Functional specifications

Process fluids
Liquid, gas, and steam applications. Fluids must be
homogeneous and single-phase.
Line sizes
Flanged style
1, 1
/
, 2, 3, 4, 6, and 8 inches
1
2
(DN 25, 40, 50, 80, 100, 150, and 200)
Pipe schedules
Process piping Schedules 10, 40, 80, and 160.
Note
The appropriate bore diameter of the process piping
must be entered using the Field Communicator or
AMS Device Manager. Meters will be shipped from
the factory at the Schedule 40 default value unless
otherwise specified.
Measurable flow rates
Capable of processing signals from flow applications which
meet the sizing requirements below.
To determine the appropriate flowmeter size for an
application, process conditions must be within the
Reynolds number and velocity limitations for the desired
line size provided in
Table
A-1,
Rosemount 8600 Vortex Flow Meter
Specifications and Reference
Data
Table
A-2, and
Table
A-3.
Specifications and Reference Data
Note
Consult your local sales representative to obtain a
computer sizing program that describes in greater
detail how to specify the correct flowmeter size for an
application.
The Reynolds number equation shown below combines the
effects of density (r), viscosity (m
(D), and flow velocity (V).
R
D
Table A-1. Minimum Measurable Meter Reynolds
Numbers
Meter Sizes
(Inches / DN)
1 through 4/25 through 100
6 through 8/150 through
200
Table A-2. Minimum Measurable Meter
Velocities
(1)
Feet per Second
Liquids
36/
Gases
36/
The  is the process fluid density at flowing conditions in
lb/ft
3
for ft/s and kg/m
3
for m/s
1.
Velocities are referenced to schedule 40 pipe.
00809-0100-4860, Rev BF
), pipe inside diameter
cp
VD 
=
----------- -
cp
Reynolds Number
Limitations
5000 minimum
Meters per
Second
54/
54/
87