Troubleshooting
May 2019
Figure 5-7. Electronics Boards Assembly
A. Electronics boards
3.
4.
5.
6.
7.
76
A
If the meter has the LCD indicator option, loosen the two screws. Remove the LCD
and the connector from the electronics board.
Loosen the three captive screws that anchor the electronics.
Use pliers or a flathead screwdriver to carefully remove the sensor cable clip from
the electronics.
Remove thermocouple if MTA option installed.
Use the handle molded into the black plastic cover to slowly pull the electronics
boards out of the housing.
Reference Manual
00809-0100-4860, Rev BF
Rosemount 8600 Vortex Flow Meter