Xenus
OUTPUT CONNECTIONS
CME2 SCREEN FOR OUTPUTS [OUT5~7]
OUTPUT DATA
[OUT6~7] SIGNALS
+30Vmax
Signal
Pins
+24V typical
[OUT6]
J5-3
+24V
[OUT7]
J5-2
HI/LO DEFINITIONS: OUTPUTS
Input
State
Condition
Output transistor is OFF
Brake is un-powered and locks motor shaft
HI
Motor cannot move
Brake state is Active
BRK-A,B
OUT6,7
Output transistor is ON
Brake is powered, releasing motor shaft
LO
Motor is free to move
Brake state is NOT-Active
CME2 Default Setting for Brake Outputs [OUT6,7] is "Brake - Active HI"
Active
= Brake is holding motor shaft (i.e. the Brake is Active)
Motor cannot move
No current flows in coil of brake
CME2 I/O Line States shows Output 6 or 7 as HI
BRK Output voltage is HI (24V), MOSFET is OFF
Servo drive output current is zero
Servo drive is disabled, PWM outputs are off
Inactive = Brake is not holding motor shaft (i.e. the Brake is Inactive)
Motor can move
Current flows in coil of brake
CME2 I/O Line States shows Output 6 or 7 as LO
BRK output voltage is LO (~0V), MOSFET is ON
Servo drive is enabled, PWM outputs are on
Servo drive output current is flowing
Copley Controls, 20 Dan Road, Canton, MA 02021, USA
Tech Support: E-mail: sales@copleycontrols.com, Web:
PLUS
2-Axis EtherCAT
NOTE: [OUT5] IS NOT AVAILABLE
ON THE 800-18782
[OUT6~7] BRAKE A,B
Tel: 781-828-8090
http://www.copleycontrols.com
800-1782
J5
24V
5
BRK-24V
4
BRK
BRK-A,B
3,2
RTN
1
[OUT6~7]
Signal
Pins
Brake A
J5-3
Brake B
J5-2
RoHS
24V
+
Fax: 781-828-6547
Page 21 of 32