Hex
Diagnostic Name and
Code
Source
6A7
Starter 1A Dry Run Test
5CE
Starter 1B Comm Loss: MP
6A8
Starter 1B Dry Run Test
5CF
Starter 2A Comm Loss: MP
6A9
Starter 2A Dry Run Test
5D0
Starter 2B Comm Loss: MP
6AA
Starter 2B Dry Run Test
CC
Starter Contactor Interrupt
Failure - Compressor 2A
CA
Starter Contactor Interrupt
Failure - Compressor
1A
CB
Starter Contactor Interrupt
Failure - Compressor 1B
CD
Starter Contactor Interrupt
Failure - Compressor 2B
180
Starter Did Not Transition –
Compressor 1A
181
Starter Did Not Transition –
Compressor 1B
182
Starter Did Not Transition –
Compressor 2A
183
Starter Did Not Transition –
Compressor 2B
6A3
Starter Failed to Arm/Start –
Cprsr 1A
6A4
Starter Failed to Arm/Start –
Cprsr 1B
6A5
Starter Failed to Arm/Start –
Cprsr 2A
6A6
Starter Failed to Arm/Start –
Cprsr 2B
1E9
Starter Fault Type I –
Compressor 1A
1 EA
Starter Fault Type I –
Compressor 1B
1 EB
Starter Fault Type I –
Compressor 2A
1EC
Starter Fault Type I –
Compressor 2B
RTAC-SVX002A-EN
Diagnostics
Severity
Persistence
Immediate
Latch
While in the Starter Dry Run Mode either 50 % Line Voltage was
sensed at the Potential Transformers or 10 % RLA Current was
sensed at the Current Transformers.
Immediate
Latch
Starter has had a loss of communication with the MP for a
15 second period.
Immediate
Latch
While in the Starter Dry Run Mode either 50 % Line Voltage was
sensed at the Potential Transformers or 10 % RLA Current was sensed
at the Current Transformers.
Immediate
Latch
Starter has had a loss of communication with the MP for a 15 second
period.
Immediate
Latch
While in the Starter Dry Run Mode either 50 % Line Voltage was
sensed at the Potential Transformers or 10 % RLA Current was sensed
at the Current Transformers.
Immediate
Latch
Starter has had a loss of communication with the MP for a 15 second
period.
Immediate
Latch
While in the Starter Dry Run Mode either 50 % Line Voltage was
sensed at the Potential Transformers or 10 % RLA Current was sensed
at the Current Transformers.
Special
Latch
Detected compressor currents greater than 10% RLA on any or all
Mode
phases when the compressor was commanded off. Detection time
shall be 5 second minimum and 10 seconds maximum. On detection
and until the controller is manually reset: generate diagnostic, energize
the appropriate alarm relay, continue to energize the Evap Pump
Output, continue to command the affected compressor off, fully unload
the effected compressor and command a normal stop to all other
compressors. For as long as current continues, perform liquid level
and fan control on the circuit effected.
Special
Latch
Same as Starter Contactor Interrupt Failure - Compressor 2A
Mode
Special
Latch
Same as Starter Contactor Interrupt Failure - Compressor 2A
Mode
Special
Latch
Same as Starter Contactor Interrupt Failure - Compressor 2A
Mode
Immediate
Latch
The Starter Module did not receive a transition complete signal in
the designated time from its command to transition. The must hold
time from the Starter Module transition command is 1 second. The
Must trip time from the transition command is 6 seconds. Actual
design is 2.5 seconds. This diagnostic is active only for YDelta, Auto-
Transformer, Primary Reactor, and X-Line Starters.
Immediate
Latch
Same as Starter Did Not Transition - Compressor 1A
Immediate
Latch
Same as Starter Did Not Transition - Compressor 1A
Immediate
Latch
Same as Starter Did Not Transition - Compressor 1A
Info
Latch
Starter failed to arm or start within the allotted time (15 seconds).
Info
Latch
Same as Starter Failed to Arm/Start - Cprsr 1A
Info
Latch
Same as Starter Failed to Arm/Start - Cprsr 1A
Info
Latch
Same as Starter Failed to Arm/Start - Cprsr 1A
Immediate
Latch
This is a specific starter test where 1M(1K1) is closed first and a check
is made to ensure that there are no currents detected by the CT's. If
currents are detected when only 1M is closed first at start, then one of
the other contactors is shorted.
Immediate
Latch
Same as Starter Fault Type I - Compressor 1A
Immediate
Latch
Same as Starter Fault Type I - Compressor 1A
Immediate
Latch
Same as Starter Fault Type I - Compressor 1A
Criteria
Reset Level
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
90