Trane R Series Installation Operation & Maintenance page 83

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Hex
Diagnostic Name and
Code
Source
5F8
Comm Loss: Evaporator
Water Pump Control
5DD
Comm Loss: External
Auto/ Stop
5E9
Comm Loss: External
Chilled Water Setpoint
5DF
Comm Loss: External
Circuit Lockout, Circuit #1
5E0
Comm Loss: External
Circuit Lockout, Circuit #2
5EA
Comm Loss: External
Current Limit Setpoint
680
Comm Loss: Fan Control
Circuit #1, Stage #1
681
Comm Loss: Fan Control
Circuit #1, Stage #2
682
Comm Loss: Fan Control
Circuit #1, Stage #3
683
Comm Loss: Fan Control
Circuit #1, Stage #4
684
Comm Loss: Fan Control
Circuit #2, Stage #1
685
Comm Loss: Fan Control
Circuit #2, Stage #2
686
Comm Loss: Fan Control
Circuit #2, Stage #3
687
Comm Loss: Fan Control
Circuit #2, Stage #4
68C
Comm Loss: Fan Inverter
Fault, Circuit #1 or Circuit
#1, Drive 1
68D
Comm Loss: Fan Inverter
Fault, Circuit #1, Drive 2
69A
Comm Loss: Fan Inverter
Fault, Circuit #2 or Circuit
#2
69B
Comm Loss: Fan Inverter
Fault, Circuit #2, Drive 2
68A
Comm Loss: Fan Inverter
Power, Circuit #1 or
Circuit #1 Drive 1 and 2
698
Comm Loss: Fan Inverter
Power, Circuit #2 or
Circuit #2 or Drive 1
and 2
68B
Comm Loss: Fan Inverter
Speed Command, Circuit
#1 or Circuit #1 Drive 1
and 2
699
Comm Loss: Fan Inverter
or Circuit #2 Drive 1 and
2 Speed Command,
Circuit #2
5D9
Comm Loss: Female Step
Load Compressor 1A
83
Diagnostics
Severity
Persistence
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch Remote
Special
Non Latch
Continual loss of communication between the MP and the Functional
Mode
ID has occurred for a 30 second period. Chiller shall discontinue use of
the External Chilled Water Setpoint source and revert to the next higher
priority for setpoint arbitration
Special
Latch
Continual loss of communication between the MP and the Functional ID
Mode
has occurred for a 30 second period. MP will nonvolatily hold the lockout
state (enabled or disabled) that was in effect at the time of comm loss.
Special
Latch
Same as Comm Loss: External Circuit Lockout, Circuit #1
Mode
Special
NonLatch
Continual loss of communication between the MP and the Functional ID
Mode
has occurred for a 30 second period. Chiller shall discontinue use of the
External Current limit setpoint and revert to the next higher priority for
Current Limit setpoint arbitration
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Special
Latch
Continual loss of communication between the MP and the Functional
Mode
ID has occurred for a 30 second period. Operate the remaining fans as
fixed speed fan deck.
Special
Latch
Same as Comm Loss: Fan Inverter Fault, Circuit #1 or Circuit #1, .Drive
Mode
1.
Special
Latch
Same as Comm Loss: Fan Inverter Fault, Circuit #1 or Circuit #1, .Drive
Mode
1.
Special
Latch
Same as Comm Loss: Fan Inverter Fault, Circuit #1 or Circuit #1, .Drive
Mode
1.
Normal
Latch
Same as Comm Loss: Fan Inverter Fault, Circuit #1 or Circuit #1, .Drive
1.
Normal
Latch
Same as Comm Loss: Fan Inverter Fault, Circuit #1 Drive 1.
Special
Latch
Same as Comm Loss: Fan Inverter Fault, Circuit #1 or Circuit #1, .Drive
Mode
1.
Special
Latch
Same as Comm Loss: Fan Inverter Fault, Circuit #1 or Circuit #1,.Drive
Mode
1.
Normal
Latch
Same as Comm Loss: Chilled Water Flow Switch
Criteria
Reset Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
RTAC-SVX002A-EN