Hex
Diagnostic Name and
Code
Source
1E6
Oil Temperature Sensor –
Cprsr 1A
1E7
Oil Temperature Sensor –
Cprsr 2A
A1
Outdoor Air Temperature
Sensor
D7
Over Voltage
19C
Phase Loss – Compressor 1A Immediate
19D
Phase Loss - Compressor 1B Immediate
19E
Phase Loss - Compressor 2A Immediate
19F
Phase Loss - Compressor 2B Immediate
184
Phase Reversal –
Compressor 1A
185
Phase Reversal –
Compressor 1B
186
Phase Reversal –
Compressor 2A
187
Phase Reversal –
Compressor 2B
1A0
Power Loss – Compressor 1A Immediate
1A1
Power Loss - Compressor 1B Immediate
1A2
Power Loss - Compressor 2A Immediate
1A3
Power Loss - Compressor 2B Immediate
8C
Pumpdown Terminated –
Circuit 1
8D
Pumpdown Terminated –
Circuit 2
1B2
Severe Current Imbalance –
Compressor 1A
1B3
Severe Current Imbalance –
Compressor 1B
1B4
Severe Current Imbalance –
Compressor 2A
1B5
Severe Current Imbalance –
Compressor 2B
5CD
Starter 1A Comm Loss: MP
89
Diagnostics
Severity
Persistence
Normal
Latch
Bad Sensor or LLID
Normal
Latch
Bad Sensor or LLID
Normal
Latch
Bad Sensor or LLID. Note that if this diagnostic occurs, operational
pumpdown will be performed regardless of the last valid temperature
Normal
NonLatch
a. Line voltage above + 10% of nominal. [Must hold = + 10 % of
nominal. Must trip = + 15 % of nominal. Reset differential = min. of
2% and max. of 4%. Time to trip = minimum of 1 min. and maximum
of 5 min.) Design: Nom. trip: 60 seconds at greater than 112.5%, + or
- 2.5%, Auto Reset at 109% or less.
Latch
a) No current was sensed on one or two of the current transformer
inputs while running or starting (See Nonlatching Power Loss
Diagnostic for all three phases lost while running). Must hold = 20%
RLA. Must trip = 5% RLA. Time to trip shall be longer than guaranteed
reset on Starter Module at a minimum, 3 seconds maximum. Actual
design trippoint is 10%. The actual design trip time is 2.64 seconds.
b) If Phase reversal protection is enabled and current is not sensed
on one or more current xformer inputs. Logic will detect and trip in a
maximum of 0.3 second from compressor start.
Latch
Same as Phase Loss - Compressor 1A
Latch
Same as Phase Loss - Compressor 1A
Latch
Same as Phase Loss - Compressor 1A
Immediate
Latch
A phase reversal was detected on the incoming current. On a
compressor startup the phase reversal logic must detect and trip in a
maximum of .3 second from compressor start.
Immediate
Latch
Same as Phase Reversal - Compressor 1A
Immediate
Latch
Same as Phase Reversal - Compressor 1A
Immediate
Latch
Same as Phase Reversal - Compressor 1A
NonLatch
The compressor had previously established currents while running
and then all three phases of current were lost. Design: Less than 10%
RLA, trip in 2.64 seconds. This diagnostic will preclude the Phase Loss
Diagnostic and the Transition Complete Input Opened Diagnostic from
being called out. To prevent this diagnostic from occurring with the
intended disconnect of main power, the minimum time to trip must be
greater than the guaranteed reset time of the Starter module.
Note: This diagnostic prevents nuisance latching diagnostics due
to a momentary power loss - It does not protect motor/compressor
from uncontrolled power reapplication. See Momentary Power Loss
Diagnostic for this protection. This diagnostic is not active during the
start mode before the transition complete input is proven. Thus a
random power loss during a start would result in either a "Starter Fault
Type 3" or a "Starter Did Not Transition" latching diagnostic.
NonLatch
Same as Power Loss - Compressor 1A
NonLatch
Same as Power Loss - Compressor 1A
NonLatch
Same as Power Loss - Compressor 1A
Info
NonLatch
The pumpdown cycle for this circuit was terminated abnormally due to
excessive time or due to a specific set of diagnostic criteria – but w/o
associated latching diagnostics
Info
NonLatch
Same as Pumpdown Terminated - Circuit 1
Immediate
Latch
A 30% Current Imbalance has been detected on one phase relative to
the average of all 3 phases for 90 continuous seconds.
Immediate
Latch
Same as Severe Current Imbalance - Compressor 1A
Immediate
Latch
Same as Severe Current Imbalance - Compressor 1A
Immediate
Latch
Same as Severe Current Imbalance - Compressor 1A
Immediate
Latch
Starter has had a loss of communication with the MP for a 15 second
period.
Criteria
Reset Level
Remote
Remote
Remote
Remote
Local
Local
Local
Local
Local
Local
Local
Local
Remote
Remote
Remote
Remote
Remote
Remote
Local
Local
Local
Local
Local
RTAC-SVX002A-EN