Controls Interface
Power-Up EasyView
Scenario #1: On Power-Up EasyView
will progress through two screens if
an application is not present.
First Screen, Version # of the Boot, only
the version # extension is displayed.
This screen will display for 3-5 seconds
and move on to the second screen.
Second Screen, Application or No Ap-
plication.
This screen will display "-APP" for as
long as it remains powered.
Scenario #2: On Power-Up EasyView
will progress through five screens if
an application is present.
First Screen, Version # of the Boot, only
the version # extension is displayed.
This screen will display for 3-5 seconds
and move on to the second screen.
Second Screen, Application or No Ap-
plication.This screen will display "APP"
for 3-5 seconds and move on to the
third screen.
Third screen, First screen of the Appli-
cation, segment and LED test.
This screen will turn on all LED's and
segments for 3-5 seconds and move on
to the fourth screen.
Fourth Screen, splash screen.
This screen will display CH530 for
3-5 seconds and move on to the fifth
screen.
Fifth Screen, the Leaving Water Tem-
perature.
Power-Up DynaView
On Power-Up, DynaView will progress
through three screens:
First Screen, Version # of the Boot, full
version # displayed.
This screen will display for 5 seconds
and move on to the second screen. The
contrast will also be adjustable from this
screen.
Second Screen, Application or No Ap-
plication.
This screen will display for 5 seconds "A
Valid Application Is Present" or "A Valid
Application Is Not Present" and move
on to the third screen.
Third Screen, First screen of the Ap-
plication, the Chiller Tab.
Self Tests
On Power-Up, the CH. 530 runs self
tests. Error messages that appear
should be recorded and reported to
a qualified service agency to include
"ERR1" or "ERR2" messages on
EasyView and a "RAM ERROR" or
"Un-Recoverable Error" message on
DynaView. Failure may result in flashing
of all the LED's on EasyView and flash-
ing of the back-light on DynaView.
Display Formats
Units
Temperature settings are in °F or °C,
depending on Display Units settings.
Settings can be entered in tenths or
whole degrees depending on a menu
setting at the TechView.
Dashes ("-----") appearing in a tempera-
ture or pressure report, indicates that
the value is invalid or not applicable.
Languages
English plus two alternate languages
may be installed with DynaView and will
reside in the main processor. English
will always be available. Alternate lan-
guages must be installed using Tech-
View, Software Download View.
TechView Interface
TechView is the PC (laptop) based tool
used for servicing Tracer CH530. Tech-
nicians that make any chiller control
modification or service any diagnostic
with Tracer CH530 must use a laptop
running the software application "Tech-
View." TechView is a Trane application
developed to minimize chiller downtime
and aid the technicians' understanding
of chiller operation and service require-
ments.
RTAC-SVX002A-EN