Trane R Series Installation Operation & Maintenance page 85

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Hex
Diagnostic Name and
Code
Source
6AB
Comm Loss: Starter Panel
High Temperature Limit –
Panel 1, Cprsr 2A
6AD
Comm Loss: Starter Panel High
Temperature Limit – Panel 2,
Cprsr 2B
6A0
Comm Loss: Status/
Annunciation Relays
5FB
Comm Loss: Suction Pressure
Cprsr 1A
5FC
Comm Loss: Suction Pressure
Cprsr 1B
5FD
Comm Loss: Suction Pressure
Cprsr 2A
5FE
Comm Loss: Suction Pressure
Cprsr 2B
2A1
Condenser Fan Variable Speed
Drive Fault – Circuit 1 (Drive 1)
5B4
Condenser Fan Variable Speed
Drive Fault – Circuit 1 Drive 2
2A2
Condenser Fan Variable Speed
Drive Fault – Circuit 2 (Drive 1)
5B5
Condenser Fan Variable Speed
Drive Fault – Circuit 2 (Drive 2)
5B8
Condenser Refrigerant Pressure
Transducer – Circuit 1
5B9
Condenser Refrigerant Pressure
Transducer – Circuit 2
FD
Emergency Stop
8E
Evaporator Entering Water
Temperature Sensor
AB
Evaporator Leaving Water
Temperature Sensor
27D
Evaporator Liquid Level Sensor
- Circuit 1
3F9
Evaporator Liquid Level Sensor
- Circuit 2
6B9
Evaporator Rfgt Drain - Circuit 1 NA
6BA
Evaporator Rfgt Drain - Circuit 2 NA
ED
EvaporatorWater Flow Lost
85
Diagnostics
Severity
Persistence
Info
Latch
Same as Comm Loss: Chilled Water Flow Switch
Info
Latch
Same as Comm Loss: Chilled Water Flow Switch
Info
Latch
Same as Comm Loss: Chilled Water Flow Switch
Immediate
Latch
Continual loss of communication between the MP and the Functional ID
has occurred for a 30 second period. Circuit target if no isolation valves,
Compressor target if isolation valves or simplex. Design Note: In the case
of manifolded compressors w/o isolation valves, the occurrence of this
diagnostic will also generate a comm loss with the nonexistent Suction
Press Cprsr 2B in order to accomplish circuit shutdown.
Immediate
Latch
Continual loss of communication between the MP and the Functional ID
has occurred for a 30 second period. Design Note: For circuits with
manifolded compressors w/o isolation valve option, this diagnostic will
occur with the preceding diagnostic, even though this transducer is
not required or installed.
Immediate
Latch
Same as Comm Loss: Suction Pressure Cprsr 1A
Immediate
Latch
Same as Comm Loss: Suction Pressure Cprsr 1B
Special
Latch
The MP has received a fault signal from the respective condenser fan
Mode
Variable Speed Inverter Drive, and unsuccessfully attempted (5 times
within 1 minute of each other) to clear the fault. The 4th attempt removes
power from the inverter to create a power up reset. If the fault does not
clear, the MP will revert to constant speed operation without the use
of the inverter's fan. The inverter must be manually bypassed, and fan
outputs rebound, for full fixed speed fan operation.
Special
Latch
Same as Condenser Fan Variable Speed Drive Fault – Circuit 1 (Drive 1)
Mode
Special
Latch
Same as Condenser Fan Variable Speed Drive Fault – Circuit 1 (Drive 1)
Mode
Special
Latch
Same as Condenser Fan Variable Speed Drive Fault – Circuit 1 (Drive 1)
Mode
Immediate
Latch
Bad Sensor or LLID
Immediate
Latch
Bad Sensor or LLID
Immediate
Latch
EMERGENCY STOP input is open. An external interlock has tripped.
Time to trip from input opening to unit stop shall be 0.1 to 1.0 seconds.
Info
Latch
Bad Sensor or LLID a. Normal operation, no effects on control. b. Chiller
shall remove any Return or Constant Return Chilled Water Reset, if it was
in effect. Apply slew rates per Chilled Water Reset spec.
Normal
Latch
Bad Sensor or LLID
Immediate
Latch
Bad Sensor or LLID
Immediate
Latch
Bad Sensor or LLID
Latch
This diagnostic is effective only with Remote Evap units. The liquid level
of the respective evaporator was not seen to be below the level of -21.2
mm (0.83 in) within 5 minutes of the commanded opening of its Drain Valve
Solenoid. The diagnostic will not be active if the drain valve is commanded
closed.
Latch
Same as Evaporator Rfgt Drain - Circuit 1
Immediate
NonLatch
a. The chilled water flow switch input was open formore than 6-10
contiguous seconds. b. This diagnostic does not de-energize the evap
pump output c. 6-10 seconds of contiguous flow shall clear this diagnostic.
d. Even though the pump times out in the STOP modes, this diagnostic
shall not be called out in the STOP modes. Note that this diagnostic will not
light the red diagnostic light on the Easy View display.
Criteria
Reset Level
Local
Local
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Local
Remote
Remote
Remote
Remote
Remote
Remote
Remote
RTAC-SVX002A-EN