Trane R Series Installation Operation & Maintenance page 134

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Fig. XII-22 – Field Layout, all - Part 1
CAUTION
HAZARDOUS VOLTAGE!
USE COPPER CONDUCTORS ONLY!
DISCONNECT ALL ELECTRIC POWER
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT
INCLUDING REMOTE DISCONNECTS
OTHER TYPES OF CONDUCTORS.
AND FOLLOW LOCK OUT AND TAG
FAILURE TO DO SO MAY CAUSE DAMAGE TO THE
PROCEDURES BEFORE SERVICING.
EQUIPMENT.
INSURE THAT ALL MOTOR
ATTENTION
CAPACITORS HAVE DISCHARGED
STORED VOLTAGE. UNITS WITH
VARIABLE SPEED DRIVE, REFER
N'UTILISER QUE DES CONDUCTEURS EN CUIVRE!
TO DRIVE INSTRUCTIONS FOR
LES BORNES DE L'UNITÉ NE SONT PAS CONÇUES
CAPACITOR DISCHARGE.
POUR RECEVOIR D'AUTRES TYPES DE CONDUCTEURS.
FAILURE TO DO THE ABOVE
L'UTILISATION DE TOUT AUTRE CONDUCTEUR PEUT
BEFORE SERVICING COULD RESULT
ENDOMMAGER L'ÉQUIPEMENT.
IN DEATH OR SERIOUS INJURY.
PRECAUCIÓN
¡UTILICE ÚNICAMENTE CONDUCTORES DE COBRE!
LAS TERMINALES DE LA UNIDAD NO ESTÁN DISEÑADAS
PARA ACEPTAR OTROS TIPOS DE CONDUCTORES.
SI NO LO HACE, PUEDE OCASIONAR DAÑO AL EQUIPO.
4
9
10
15
TRANE TRACER
11
OR
OTHER REMOTE DEVICE
(OPTIONAL)
SHIELDED TWISTED PAIR LEADS
11
LINK TO NEXT UNIT
(OPTIONAL)
SHIELDED TWISTED PAIR LEADS
START STOP ICE MAKING
(OPTIONAL)
2 WIRES
BINARY INPUT TO UNIT . CONTACT
CLOSURE ENABLES ICE MAKING
CURRENT LIMIT SETPOINT
(OPTIONAL)
3 WIRES MAXIMUM
2-10 VOLT OR 4-20 mA INPUT
TO UNIT
CHILLED WATER SETPOINT
(OPTIONAL)
3 WIRES MAXIMUM
2-10 VOLT OR 4-20 mA INPUT
TO UNIT
EXTERNAL LOCKOUT
CIRCUIT #1
2 WIRES
BINARY INPUT TO UNIT .
OPEN CONTACTS ENABLE UNIT
OPERATION
EXTERNAL LOCKOUT
CIRCUIT #2
2 WIRES
BINARY INPUT TO UNIT .
OPEN CONTACTS ENABLE UNIT
OPERATION
12
AUTO STOP
2 WIRES
BINARY INPUT TO UNIT .
CLOSED CONTACTS ENABLE UNIT
OPERATION
12
EMERGENCY STOP
2 WIRES
BINARY INPUT TO UNIT .
CLOSED CONTACTS ENABLE UNIT
OPERATION
RTAC-SVX002A-EN
Wiring Diagram
WARNING
AVERTISSEMENT
TENSION DANGEREUSE!
COUPER TOUTES LES TENSIONS ET
OUVRIR LES SECTIONNEURS À DISTANCE,
PUIS SUIVRE LES PROCÉDURES DE
VERROUILLAGE ET DES ÉTIQUETTES AVANT
TOUTE INTERVENTION. VÉRIFIER QUE TOUS
LES CONDENSATEURS DES MOTEURS SONT
DÉCHARGÉS. DANS LE CAS D'UNITÉS
COMPORTANT DES ENTRAÎNEMENTS À
VITESSE VARIABLE, SE REPORTER AUX
INSTRUCTIONS DE L'ENTRAÎNEMENT POUR
DÉCHARGER LES CONDENSATEURS.
NE PAS RESPECTER CES MESURES DE
PRÉCAUTION PEUT ENTRAÎNER DES
BLESSURES GRAVES POUVANT ÊTRE
MORTELLES.
CHILLED WATER
PUMP
CHILLED WATER
3
FLOW SWITCH
ICE MAKING STATUS
(OPTIONAL)
13
3 WIRES & GROUND IF REQUIRED
14
TO NORMALLY OPEN CONTACTS
WHICH CLOSE WHEN ICE BUILD
IS COMPLETE
ALARM INDICATOR
(OPTIONAL)
3 WIRES MINIMUM &
13
GROUND IF REQUIRED
14
ALARM INDICATOR
17
(OPTIONAL)
3 WIRES MINIMUM &
GROUND IF REQUIRED
3
UNIT OPERATION
INDICATER
(OPTIONAL)
4
13
3 WIRES MINIMUM &
GROUND IF REQUIRED
14
UNIT OPERATION
17
INDICATER
(OPTIONAL)
3 WIRES MINIMUM &
GROUND IF REQUIRED
MAXIMUM UNIT CAPACITY
INDICATOR
(OPTIONAL)
3 WIRES MINIMUM &
13
GROUND IF REQUIRED
14
MAXIMUM UNIT CAPACITY
17
INDICATOR
(OPTIONAL)
6.
3 WIRES MINIMUM &
GROUND IF REQUIRED
7
LIMITED UNIT OPERATION
8
INDICATOR
(OPTIONAL)
13
3 WIRES MINIMUM &
9
GROUND IF REQUIRED
14
LIMITED UNIT OPERATION
17
INDICATOR
(OPTIONAL)
10
3 WIRES MINIMUM &
GROUND IF REQUIRED
11
12
EVAPORATOR HEATER
13
AND/OR
8
CONVENIENCE OUTLET
13
(OPTIONAL)
2 WIRES & GROUND IF REQUIRED
14
CHILLED WATER PUMP
AUXILIARY & FLOW
15
SWITCH INTERLOCKS
16
16
3 WIRES
BINARY INPUTS TO UNIT.
17
CONTACT CLOSURE INDICATES
CHILLED WATER FLOW
TRANE CHILLED WATER
3
PUMP CONTROL
13
3 WIRES MINIMUM &
14
GROUND IF REQUIRED
ADVERTENCIA
iVOLTAJE PELIGROSO!
DESCONECTE TODA LA ENERGÍA ELÉCTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y
SIGA LOS PROCEDIMIENTOS DE CIERRE Y
ETIQUETADO ANTES DE PROCEDER AL
SERVICIO. ASEGÚRESE DE QUE TODOS
LOS CAPACITORES DEL MOTOR HAYAN
DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON EJE DE
DIRECCIÓN DE VELOCIDAD VARIABLE,
CONSULTE LAS INSTRUCCIONES PARA LA
DESCARGA DEL CONDENSADOR.
EL NO REALIZAR LO ANTERIORMENTE
INDICADO, PODRÍA OCASIONAR LA MUERTE
O SERIAS LESIONES PERSONALES.
CUSTOMER
ENTRANCE
(REAR 6 KNOCKOUTS
4
9
(FRONT 6 KNOCKOUTS
GENERAL NOTES:
1.
CAUTION-DO NOT ENERGIZE THE UNIT UNTIL CHECK OUT AND STARTUP PROCEDURES HAVE BEEN COMPLETED.
2.
ALL MOTORS ARE PROTECTED FROM PRIMARY SINGLE PHASE FAILURES.
CAUTION - TRANE PUMP CONTROL MUST BE USED TO PROVIDE PUMP CONTROL. EVAPORATOR CHILLED WATER
PUMP MUST BE CONTROLLED BY THE CHILLER OUTPUT. FAILURE TO COMPLY WITH THIS REQUIREMENT
MAY RESULT IN DAMAGE TO THE UNIT.
THE FOLLOWING FEATURES ARE OPTIONAL AND MAY OR MAY NOT BE PROVIDED. CUSTOMER PROVIDED WIRING FOR ALL STANDARD
FEATURES AND OPTIONS IS SHOWN ON THIS DIAGRAM. OPTIONAL FEATURES ARE SO NOTED.
LOW VOLTAGE OPTIONAL (CLASS 2)
TRACER COMMUNICATION INTERFACE
ICE MAKING START/STOP
EXTERNAL CURRENT LIMIT AND EXTERNAL CHILLED WATER SETPOINT
115 VOLT OPTIONS FOR 60HZ UNITS OR 220 VOLT OPTIONS FOR 50HZ UNITS.
ICE MAKING STATUS
UNIT OPERATING STATUS MODULE
EVAPORATOR HEATER (FREEZE PROTECTION). STANDARD WITH UNIT-
MOUNTED EVAPORATOR. NOT USED WITH REMOTE EVAPORATOR OPTION.
CONVENIENCE OUTLET
LINE VOLTAGE OPTIONS
UNIT MOUNTED TERMINAL BLOCK, DISCONNECT OR HACR CIRCUIT BREAKER
SINGLE SOURCE POWER IS PROVIDED AS STANDARD. DUAL SOURCE POWER IS AVAILABLE AS AN OPTION.
WIRING REQUIREMENTS
5.
RECOMMENDED FIELD WIRING CONNECTIONS ARE SHOWN BY DOTTED LINES
ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE AND STATE AND LOCAL REQUIREMENTS.
EXPORT UNIT WIRING MUST COMPLY WITH LOCAL APPLICABLE CODES.
ALL UNIT POWER WIRING MUST BE COPPER CONDUCTORS ONLY AND HAVE A MINIMUM TEMPERATURE INSULATION RATING OF
90 DEGREE C. SEE UNIT NAMEPLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM FUSE SIZE REQUIREMENTS. THE POWER
WIRING LUG SIZE PROVIDED ON THE VARIOUS UNITS IS SHOWN IN THE TABLE BELOW.
POWER FOR THE EVAPORATOR HEATER AND/OR OPTIONAL CONVENIENCE OUTLET IS SUPPLIED BY A COMMON CUSTOMER PROVIDED POWER
SUPPLY. WHEN POWERED, THE HEAT TAPE WILL USE 1640 VA OF THE TOTAL AVAILABLE SUPPLY ON 60HZ UNITS AND APPROXIMATELY
1390 VA ON 50 HZ UNITS. EVAPORATOR HEATERS ARE NOT PROVIDED WITH REMOTE EVAPORATOR UNITS.
ALL CUSTOMER CONTROL CIRCUIT WIRING MUST BE COPPER CONDUCTORS ONLY AND HAVE A MINIMUM INSULATION RATING OF 300 VOLTS.
EXCEPT AS NOTED ALL CUSTOMER WIRING CONNECTIONS ARE MADE TO CIRCUIT BOARD MOUNTED BOX LUGS WITH A WIRE RANGE OF 14
TO 18 AWG. THE HEAT TAPE AND/OR CONVENIENCE OUTLET AND THE GROUND SIDE OF THE FLOW SWITCH GO TO TERMINAL STRIPS WITH A
#10 SET SCREW WHICH WILL ACCEPT RING OR FORK TERMINALS OR STRIPPED WIRE LEADS.
DO NOT RUN LOW VOLTAGE CONTROL WIRING (30 VOLTS OR LESS) IN CONDUIT WITH 110 VOLT OR HIGHER WIRING. DO NOT EXCEED
THE FOLLOWING MAXIMUM RUN LENGTHS FOR A GIVEN SIZE: 14 AWG, 5000 FT; 16 AWG, 2000 FT; 18 AWG, 1000FT
SHIELDED TWISTED PAIR LEADS ARE REQUIRED FOR CONNECTIONS TO THE COMMUNICATIONS INTERFACE MODULE (1U8). THE
SHIELD SHOULD BE GROUNDED AT THE RTAC CONTROL PANEL END.
THE CONTACTS FOR THESE FEATURES ARE JUMPERED AT THE FACTORY BY JUMPERS W1 & W2 TO ENABLE UNIT OPERATION. IF
IF REMOTE CONTROL IS DESIRED REMOVE THE NOTED JUMPERS AND CONNECT TO THE DESIRED CONTROL CIRCUIT.
FIELD PROVIDED 115 VOLT 60HZ OR 220 VOLT 50HZ CONTROL POWER SUPPLIES ARE REQUIRED. THE MAX FUSE SIZE FOR EVAPORATOR HEATER
AND CONVENIENCE OUTLET IS 20 AMPS ON 115 VOLT 60HZ PRODUCTS AND 15 AMPS ON 220 VOLT 50 HZ PRODUCTS. THE MAX FUSE SIZE FOR
ALL OTHER FIELD PROVIDED CIRCUITS IS 15 AMPS. GROUND ALL CUSTOMER PROVIDED POWER SUPPLIES AS REQUIRED BY CODE. GREEN GROUND
SCREWS ARE PROVIDED IN UNIT CONTROL PANEL.
CONTACT RATINGS AND REQUIREMENTS
UNIT PROVIDED DRY CONTACTS FOR THE EVAPORATOR PUMP CONTROL, THE UNIT OPERATING STATUS RELAYS AND ICE MAKING STATUS RELAY
ARE RATED FOR 7.2 AMPS RESISTIVE, 2.88 AMPS PILOT DUTY, OR 1/3 HP, 7.2 FLA AT 120 VOLTS 60 HZ, CONTACTS ARE RATED FOR 5 AMPS
GENERAL PURPOSE DUTY AT 240 VOLTS.
CUSTOMER SUPPLIED CONTACTS FOR ALL CLASS 2 CONNECTIONS MUST BE COMPATABLE WITH DRY CIRCUIT 24 VOLTS DC
FOR A 12 MA RESISTIVE LOAD. SILVER OR GOLD PLATED CONTACTS ARE RECOMMENDED.
FLOW SWITCH & INTERLOCK CONTACTS MUST BE ACCEPTABLE FOR USE IN A 120 VOLT 1 mA CIRCUIT OR A 220 VOLT 2 mA CIRCUT.
THE FIELD PROVIDED INDICATORS MAY BE RELAYS, LIGHTS OR AUDIBLE DEVICES. FOUR DUPLICATE INDICATOR FUNCTIONS ARE SHOWN.
THE DUPLICATE FUNCTIONS MAY BE CONNECTED TO EITHER OR BOTH OF THE NORMALLY OPEN OR NORMALLY CLOSED RELAY CONTACTS
OF EACH OF THE 4 SPDT RELAYS ON THE OPTIONAL UNIT OPERATING STATUS MODULE.
THE FUNCTIONS OF THE OPERATING STATUS MODULE RELAYS ARE PROGRAMABLE. SEE IOM FOR DETAILS. DEFAULT FUNCTIONS ARE SHOWN.
THE NORMALLY OPEN CONTACTS ON EACH RELAY OPERATE AS FOLLOWS:
CONTACTS TO THE ALARM INDICATOR CLOSE ON A UNIT MALFUNCTION.
CONTACTS TH THE UNIT OPERATION INDICATOR CLOSE WHEN ANY COMPRESSOR IS RUNNING.
CONTACTS TO THE MAX UNIT CAPACITY INDICATOR CLOSE WHEN ALL UNIT COMPRESSORS ARE FULLY LOADED.
CONTACTS TO THE LIMITED UNIT OPERATION INDICATOR CLOSE IF NORMAL UNIT OPERATION IS RESTRICTED BY SOME OPERATING PARAMETER.
EVAPORATOR MAY
BE UNIT OR REMOTE
MOUNTED
CLASS 2
WIRING
EVAPORATOR
CHILLER
LINE VOLTAGE
IN PANEL)
UNIT POWER SUPPLY
115V
SINGLE OR
CUSTOMER
WIRING
DUAL SOURCE
ENTRANCE
IN PANEL)
4
7
134