Trane R Series Installation Operation & Maintenance page 92

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Hex
Diagnostic Name and Source
Code
5B0
Transition Complete Input
Opened - Compressor 1A
5B1
Transition Complete Input
Opened - Compressor
1B
5B2
Transition Complete Input
Opened - Compressor 2A
5B3
Transition Complete Input
Opened - Compressor
2B
5AC
Transition Complete Input
Shorted - Compressor 1A
5AD
Transition Complete Input
Shorted - Compressor 1B
5AE
Transition Complete Input
Shorted - Compressor 2A
5AF
Transition Complete Input
Shorted - Compressor 2B
D8
Under Voltage
771
Very Low Evaporator
Refrigerant Pressure – Circuit 1
772
Very Low Evaporator
Refrigerant Pressure – Circuit 2
RTAC-SVX002A-EN
Diagnostics
Severity
Persistence
Immediate
Latch
The Transition Complete input was found to be opened with the
compressor motor running after a successful completion of transition.
This is active only for YDelta, Auto-Transformer, Primary Reactor, and
X- Line Starters. To prevent this diagnostic from occurring as the result
of a power loss to the contactors, the minimum time to trip must be
greater than the trip time for the power loss diagnostic.
Immediate
Latch
Same as Transition Complete Input Opened - Compressor 1A
Immediate
Latch
Same as Transition Complete Input Opened - Compressor 1A
Immediate
Latch
Same as Transition Complete Input Opened - Compressor 1A
Immediate
Latch
The Transition Complete input was found to be shorted before the
compressor was started. This is active for all electromechanical
starters.
Immediate
Latch
Same as Transition Complete Input Opened - Compressor 2B
Immediate
Latch
Same as Transition Complete Input Opened - Compressor 2B
Immediate
Latch
Same as Transition Complete Input Opened - Compressor 2B
Normal
NonLatch
a. Line voltage below - 10% of nominal or the Under/Overvoltage
transformer is not connected. [Must hold = - 10 % of nominal.
Must trip = - 15 % of nominal. Reset differential = min. of 2% and max.
of 4%. Time to trip = min. of 1 min. and max. of 5 min.) Design: Nom.
trip: 60 seconds at less than 87.5%, + or - 2.8% at 200V or + or - 1.8%
at 575V, Auto Reset at 90% or greater.
Immediate
Latch
The evaporator pressure dropped below 10 psia (or 5 psia in software
prior to Oct '02)regardless of whether or not compressors are running
on that circuit. This diagnostic was created to prevent compressor
failures due to crossbinding by forcing an entire chiller shutdown. If
a given compressor or circuit is locked out, the suction pressure
transducer(s)associated with it, will be excluded from causing this
diagnostic.
Immediate
Latch
Same as Very Low Evaporator Refrigerant Pressure - Circuit 1
Criteria
Reset Level
Local
Local
Local
Local
Local
Local
Local
Local
Remote
Local
Local
92