Page 3
Contents Installation - Electrical General Recommendations Wire Sizing Electrical Data Tables Installer-Supplied Components Power Supply Wiring Control Power Supply Heater Power Supply Water Pump Power Supply Interconnecting Wiring Alarm and Status Relay Outputs (Programmable Relays) Relay Assignments Using TechView Low Voltage Wiring Emergency Stop External Auto/Stop External Circuit Lockout...
Page 4
Contents Pre-Start Checkout Installation Checklist General Unit Voltage Power Supply Unit Voltage Imbalance Unit Voltage Phasing Water System Flow Rates Water System Pressure Drop Ch.530 Set-up Unit Startup Procedures Daily Unit Startup General Seasonal Unit Startup Procedure System Restart After Extended Shutdown Unit Shutdown Procedures Temporary Shutdown And Restart Extended Shutdown Procedure...
Page 5
Contents Periodic Maintenance Maintenance Procedures Refrigerant Emission Control Refrigerant and Oil Charge Management Charge Isolation in the high or low side of system Filter Replacement Procedure Lubrication System Prelubrication Field Oil Charging Procedure RLC-SVX02G-E4...
72 hours of delivery. Notify the local TRANE sales office at the same time. Loose Parts Inventory Important notice: No shipping Check all the accessories and loose...
General Data SI Units Table G-1 - General Data RTAC 140-200 Standard Size Cooling capacity (5) (6) 491.9 537.3 585.4 648.0 714.5 Power input (7) 170.1 187.8 224.7 244.2 Energy Efficiency Ratio (5) (6) (as Eurovent) kW/kW 2.89 2.86 2.84 2.89 2.93 ESEER (as Eurovent)
Page 8
General Data SI Units Table G-2 - General Data RTAC 120-200 High Efficiency Size Cooling capacity (5) (6) 421.9 465.9 513.3 557.3 603.7 669.8 740.1 Power input (7) 137.5 151.4 165.7 182.7 200.3 219.1 238.7 Energy Efficiency Ratio (5) (6) (as Eurovent) kW/kW 3.07 3.08...
Page 9
General Data SI Units Table G-3 - General Data RTAC 120-200 Extra Efficiency Size Cooling capacity (5) (6) 426.8 474.7 520.7 566.4 632.8 679.6 747.1 Power input (7) 135.1 149.7 164.8 179.8 198.4 215.7 236.4 Energy Efficiency Ratio (5) (6) (as Eurovent) kW/kW 3.16 3.17...
Page 10
General Data SI Units Table G-4 - General Data RTAC 140-200 Low Noise Standard Size Cooling capacity (5) (6) 465.9 508.8 554.5 614.3 677.9 Power input (7) 178.2 196.1 214.9 234.3 254.6 Energy Efficiency Ratio (5) (6) (as Eurovent) kW/kW 2.61 2.58 2.62...
Page 11
General Data SI Units Table G-5 - General Data RTAC 120-200 High Efficiency Low Noise Size Cooling capacity (5) (6) 405.0 447.6 493.3 535.5 580.1 643.8 711.3 Power input (7) 155.1 169.8 186.8 204.3 223.8 244.2 Energy Efficiency Ratio (5) (6) (as Eurovent) kW/kW 2.88...
Page 12
General Data SI Units Table G-6 - General Data RTAC 120-200 Extra Efficiency Low Noise Size Cooling capacity (5) (6) 412.7 459.2 501.7 548.8 611.8 657.1 718.7 Power input (7) 135.1 149.7 164.8 179.8 198.4 215.7 236.4 Energy Efficiency Ratio (5) (6) (as Eurovent) kW/kW 3.01 3.03...
Page 13
General Data SI Units Table G-7 - General Data RTAC 230-400 Standard Size Cooling capacity (5) (6) 769.7 857.9 850.9 947.2 1077.3 1191.6 1322.4 1451.4 Power input (7) 293.6 293.4 330.5 370.2 418.9 458.8 498.4 Energy Efficiency Ratio (5) (6) (as Eurovent) kW/kW 2.93...
Page 14
General Data SI Units Table G-8 - General Data RTAC 250-400 High Efficiency Size Cooling capacity (5) (6) 876.9 978.5 1111.8 1227.8 1363.9 1501.3 Power input (7) 289.8 360.2 407.2 446.9 486.9 Energy Efficiency Ratio (5) (6) (as Eurovent) kW/kW 3.03 3.05 3.09...
Page 15
General Data SI Units Table G-9 - General Data RTAC 255-400 Extra Efficiency Size Cooling capacity (5) (6) 898.7 998.2 1128.3 1290.0 1388.1 1516.8 Power input (7) 283.5 318.9 355.9 408.2 444.9 481.5 Energy Efficiency Ratio (5) (6) (as Eurovent) kW/kW 3.17 3.13...
Page 16
General Data SI Units Table G-10 - General Data RTAC 230-400 Low Noise Standard Size Cooling capacity (5) (6) 728.9 798.1 806.6 897.6 1021.8 1127.2 1252.4 1375.8 Power input (7) 271.9 309.6 306.7 344.6 385.7 478.5 519.6 Energy Efficiency Ratio (5) (6) (as Eurovent) kW/kW 2.68...
Page 17
General Data SI Units Table G-11 - General Data RTAC 250-400 High Efficiency Low Noise Size Cooling capacity (5) (6) 838.6 940.9 1068.9 1179.3 1310.1 1442.3 Power input (7) 328.3 368.9 415.6 456.6 498.1 Energy Efficiency Ratio (5) (6) (as Eurovent) kW/kW 2.81 2.87...
Page 18
General Data SI Units Table G-12 - General Data RTAC 255-400 Extra Efficiency Low Noise Size Cooling capacity (5) (6) 867.4 966.5 1090.3 1239.7 1334.3 1456.7 Power input (7) 292.1 324.3 363.4 418.8 455.4 495.5 Energy Efficiency Ratio (5) (6) (as Eurovent) kW/kW 2.97 2.98...
Installation - Mechanical Installation Storage Responsibilities Extended storage of the unit prior to installation requires the following Generally, the contractor must do precautionary measures: the following when installing an RTAC unit: 1. Store the unit in a secure area. [ ] Install the unit on a flat 2.
Installation - Mechanical Special Lifting and Moving CAUTION Instructions A specific lifting method is 4.This unit must be lifted with the recommended as follows: utmost care. Avoid shock load by lifting slowly and evenly. 1. Lifting points are built into the unit.
General Data Section for operating weights. After it is in place, the unit must be level within 1/4" [6 mm] over its length and width. Trane is not responsible for equipment problems resulting from an improperly designed or constructed foundation.
Install isolators. shutoff valves on both the entering- Trane assumes no responsibility for and leaving-water lines so that the Lower the unit onto the isolators equipment failures which results...
2. To prevent switch fluttering, [ ] Flow Proving Device Neither salt nor brackish water is remove all air from the water recommended for use in Trane air- system. cooled Series R chillers. Use of CAUTION either will lead to a shortened life to Note: The CH.530 provides a...
Installation - Mechanical Water Pressure Gauges Install field-supplied pressure components as shown in Figure 5. Locate pressure gauges or taps in a straight run of pipe; avoid placement near elbows, and so forth. Be sure to install the gauges at the same elevation on each shell if the shells have opposite-end water connections.
1. Additional protection must be to overheat. fitted - contact your Trane Sales It is compulsory to open the heaters Office. switch to protect them from 2. Install heat tape on all water...
Page 37
Installation - Mechanical Chart 3 – Recommended Low Evaporator Refrigerant Cutout (LRTC) and % Glycol for RTAC Chillers Propylene Glycol Ethylene Glycol Low Refrigerant Solution Low Refrigerant Solution Temperature Freeze Temperature Freeze Glycol Cutout °C Point °C Cutout °C Point °C -2.2 -2.2 -2.4...
Page 38
Installation - Mechanical Notes for Chart 3: Specials: 1. Solution freeze point is 2.2°C 1. The following constitute a special below operating point saturation that must be calculated by temperature. engineering: • Freeze inhibitor other than 2. LRTC is 2.2°C below freeze point. Ethylene Glycol or Propylene Procedure: Glycol.
Installation – Electrical General Recommendations CAUTION WARNING To avoid corrosion and overheating at terminal connections, use copper mono-conductors only. Failure to do The Warning Label shown in Figure so may result in damage to the 6 is displayed on the equipment and equipment.
Wire Sizing Table J-1 - Customer Wire Selection RTAC 120 - 200 Unit without Unit with Disconnect Switch Disconnect Switch Voltage Wire Selection Size to 400/3/50 Main Terminal Block Wire Selection Size to Disconnect Switch Unit Unit Maximum cable Disconnect Switch Maximum cable size mm²...
Page 41
Wire Sizing Table J-2 - Customer Wire Selection RTAC 230 - 400 Unit without Unit with Disconnect Switch Disconnect Switch Voltage Wire Selection Size to 400/3/50 Main Terminal Block Wire Selection Size to Disconnect Switch Unit Unit Maximum cable Disconnect Switch Maximum cable Size Size...
Electrical Data Table E-1 - Electrical Data RTAC 120 - 200 ( 400/3/50) Motor Data Compressor (Each) Fans (Each) (6) Starting Fan fuse Control Maximum Evaporator Amps (4) size (A) (VA) Amps (3) heater Unit Size Quantity cmpr 1 cmpr 2 cmpr 1 cmpr 2 Quantity...
Page 43
Electrical Data Table E-1 - Electrical Data RTAC 230 - 400 ( 400/3/50) Compressor (Each) Fans (Each) (6) Maximum Amps (3) Starting Amps (4) Starting amps, Direct on line start (7) Unit cmpr cmpr cmpr cmpr cmpr cmpr cmpr cmpr cmpr cmpr cmpr...
Page 44
Electrical Data Table E-2 - Electrical Data RTAC 120 - 200 Unit Wiring (400/3/50) Motor Data Compressor (Each) Unit Starting Starting Amps (2) (7) Power Compressor Short Circuit Number of Power Maximum size Connections Amps (1) Amps (2) Direct on line start Factor (5) Fuse Size (A) Rating (kA)
Page 45
Electrical Data Table E-2 - Electrical Data RTAC 120 - 200 Unit Wiring (400/3/50) Motor Data Compressor (Each) Unit Number of Power Maximum Starting Starting Amps (2) (7) Power Compressor Short Circuit size Connections Amps (1) Amps (2) Factor (5) Fuse Size (A) Direct on line start Rating (kA)
CH530 activates the The type and installation location(s) pumps.. of the fused-disconnect switches must comply with all applicable codes. For temperatures below -29°C, please contact your local Trane sales engineer for advice. RLC-SVX02G-E4...
Installation – Electrical Table 12 – Pump Relay Operation Water Pump Power Supply Chiller Mode Relay Operation CAUTION Provide power-supply wiring with Auto Instant close Ice Building Instant close fused disconnect switch(es) for the Refer to Freeze Protection section Tracer Override Close chilled-water pump(s).
Installation – Electrical Alarm and Status Relay Outputs (Programmable Relays) A programmable relay concept provides for enunciation of certain events or states of the chiller, selected from a list of likely needs, while only using four physical output relays as shown in the field wiring diagram. The four relays are provided (generally with a Quad Relay Output LLID) as part of the Alarm Relay Output.
Installation – Electrical Relay Assignments Using Emergency Stop TechView The CH.530 provides auxiliary control for a customer-specified and The CH.530 Service Tool (TechView) -installed latching tripout. When this is used to assign any of the above customer-furnished remote contact list of events or status to each of the (6S3) is provided, the chiller will run four relays provided.
Installation – Electrical External Circuit Lockout – Ice-Building Option CAUTION Circuit Number 1 and The CH.530 provides auxiliary control for a customer-specified and Circuit Number 2 Freeze inhibitor must be adequate -installed contact closure for ice for the leaving-water temperature. The CH.530 provides auxiliary building, if so configured and Failure to do so will result in...
Installation – Electrical The chilled-water set point may be If the ECWS LLID develops an open Optional External Chilled- changed from a remote location by or short, the LLID will report either a Water Set Point (ECWS): sending either a 2-10 V (dc) or very high or very low value back to The CH.530 provides inputs that 4-20 mA signal to the (A2-1) module.
Page 52
Installation – Electrical The following equations apply: For RTAC Units Voltage Signal Current Signal As generated from external source Vdc=0.133*(%)-6.0 mA=0.266*(%)-12.0 As processed by Tracer CH530 % = 7.5*(VDC)+45.0 % = 3.75*(mA)+45.0 As a graph this yields the following: For input signals beyond the 2- 10VDC or 4-20mA range, the end of range value is used.
Installation – Electrical 6. Connect TechView to the Tracer Optional Tracer Comm 3 Communication Link Connection CH.530 controller. Procedure Interface 7. Look at the Feature tab in 1. Refer to the Tracer installation This option allows the Tracer CH.530 Configuration View-Custom Tab literature to determine proper controller to exchange information in TechView and verify that the...
- 105 ohms at each end for Level 4 between a LonTalk compatible wire device and the chiller. The - 82 ohms at each end for Trane inputs/outputs include both "purple" wire mandatory and optional network variables as established by the •...
Page 56
Operating Principles Figure 8 – RTAC Oil System CAUTION The RTAC units must only operate with R-134a and Trane OIL 00048E. Key: Refrigerant with small amount of oil Refrigerant and oil mixture (refrigerant vapor and oil) Oil recovery system (liquid refrigerant and oil) Primary oil system 1.
Pre-Start Checkout Installation Checklist CAUTION CAUTION Complete this checklist as the unit is installed, and verify that all If using an acidic, commercial To avoid corrosion and overheating recommended procedures are flushing solution, construct a at terminal connections, use only accomplished before the unit is temporary bypass around the unit copper conductors.
If the measured voltage on undervoltage conditions at the treatment, if any, is advisable. Trane any leg is not within the specified compressor motor. warranty specifically excludes range, notify the supplier of the liability of corrosion, erosion, or 2.
Pre-Start Checkout This direction may be reversed Unit Voltage Imbalance CAUTION outside the alternator by Excessive voltage imbalance interchanging any two of the line between the phases of a three- wires. It is this possible interchange Do not interchange any load leads phase system can cause motors to of wiring that makes a phase that are from the unit contactors or...
(HFC 134a) and for the chilled-water pump. excessive pressure drop in the Trane Oil 0048E. Failure to do so Energize the pump(s) to start liquid line, or an expansion valve may cause compressor damage and water circulation.
Unit Startup Procedures Seasonal Unit Startup CAUTION Procedure 1. Close all valves and reinstall the To prevent damage to the drain plugs in the evaporator. compressor, ensure that all refrigerant valves are open before 2. Service the auxiliary equipment starting the unit. according to the startup and 2.
Unit Shutdown Procedures Temporary Shutdown and CAUTION Restart To shut the unit down for a short Lock the chilled-water pump time, use the following procedure: disconnects open to prevent pump damage. 1. Press the STOP key on the 3. Close all chilled-water supply CH.530.
Periodic Maintenance 3. Have Trane or another qualified General laboratory perform a compressor Perform all maintenance procedures oil analysis to determine system and inspections at the moisture content and acid level. recommended intervals. This will This analysis is a valuable prolong the life of the chiller and diagnostic tool.
Evaporator Temperature) Conservation and emission as gauges, hoses, vacuum reduction can be accomplished by • Low Evaporator-Refrigerant following recommended Trane pumps, and recycling equipment. Temperature Limit operation, maintenance, and service 7. Stay aware of unit enhancements, • Low Refrigerant-Temperature...
Page 65
Maintenance Procedures Some symptoms of an oil over- CAUTION charged unit: • Larger-than-normal evaporator Water must be flowing through the approach temperatures (Leaving- evaporator during the entire Water Temperature - Saturated- charging process to avoid freezing Evaporator Temperature) and rupturing of the evaporator •...
The service tool may include a 8. Remove the remainder of the calculation module that determines charge with the vacuum pump. the proper subcooling for any operating condition (Trane Service Recommendation: Do not pump only). the remaining charge into the high side. This may introduce...
Page 67
Maintenance Procedures Table 15 – Charge-Holding Capability on The High Side Normal Circuit *Condenser Charge-Holding Nominal Circuit Charge in Oil Charge Capacity Capacity at 60% full, 35°C ambient Oil Separator Separator (kg) (kg) Level (tons) (liters) 74.8 53.6 21.3 97.70% 74.8 53.6 21.3...
7. Remove the old filter element. 8. Inspect the replacement filter element and lubricate the o-ring with Trane OIL 0048E. Note: Do not use mineral oil. It will contaminate the system. 9. Install the new filter element in the filter housing.
Page 69
Maintenance Procedures Proper charging of the oil system is Figure 9 – Oil System Schematic critical to the reliability of the compressor and chiller. Too little oil can cause the compressor to run hot and inefficiently. When taken to an extreme, low oil level may result in instant failure of the compressor.
The only issue is that if the schraeder valve is not present on this port, the 7/16 o-ring boss plug normally in this location will have to be replaced by a 7/16- schraeder fitting (Trane part number RLC-SVX02G-E4...
Use only Trane Oil 0048E in the RTAC units to avoid any Note: this procedure can be catastrophic damage to the followed even with the refrigerant compressor or unit.
Page 72
Maintenance Procedures If oil was removed to service a WARNING compressor or change the filter follow this procedure: Catastrophic damage to the 1. If the compressor is a new compressor will occur if the oil-line compressor or has been removed shutoff valve or the isolation valves from the system and reworked, are left closed on unit startup.
Supersedes RLC-SVX02F-E4_0409 Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this publication.
Need help?
Do you have a question about the R Series and is the answer not in the manual?
Questions and answers