Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Hex
Diagnostic Name and
Code
Source
5BE
Intermediate Oil Pressure
Compressor 2A
BF
High Pressure Cutout –
Compressor 2B
5BE
Intermediate Oil Pressure
Transducer - Compressor 1A
5BF
Intermediate Oil Pressure
Transducer - Compressor
1B
5C0
Intermediate Oil Pressure
Transducer - Compressor 2A
5C1
Intermediate Oil Pressure
Transducer - Compressor 2B
C5
Low Chilled Water Temp:
Unit Off
C6
Low Chilled Water Temp:
Unit On
1AE
Low Differential Refrigerant
Pressure - Circuit 1
1AF
Low Differential Refrigerant
Pressure - Circuit 2
583
Low Evaporator Liquid Level
- Circuit 1
5B6
Low Evaporator Liquid Level
- Circuit 2
194
Low Evaporator Refrigerant
Temperature - Circuit 1
195
Low Evaporator Refrigerant
Temperature - Circuit 2
6B3
Low Evaporator Temp – Ckt
1: Unit Off
6B3
Low Evaporator Temp – Ckt
2: Unit Off
198
Low Oil Flow – Compressor
1A
87
Diagnostics
Severity
Persistence
Immediate
Latch
Bad Sensor or LLID
Immediate
Latch
Same as High Pressure Cutout - Compressor 1A
Immediate
Latch
Bad Sensor or LLID
Immediate
Latch
Bad Sensor or LLID
Immediate
Latch
Bad Sensor or LLID
Immediate
Latch
Bad Sensor or LLID
Special
NonLatch
The leaving chilled water temp. fell below the leaving water temp
Mode
cutout setting for 30 degree F seconds while the Chiller is in the Stop
mode, or in Auto mode with no compressors running. Energize Evap
Water pump Relay until diagnostic auto resets, then return to normal
evap pump control. Automatic reset occurs when the temp rises 2°F
(1.1°C) above the cutout setting for 30 minutes.
Immediate
NonLatch
The chilled water temp. fell below the cutout setpoint for 30 degree F
and Special
Seconds while the compressor was running. Automatic reset occurs
Mode
when the temperature rises 2 °F (1.1°C) above the cutout setting for 2
minutes. This diagnostic shall not de-energize the Evaporator
Water Pump Output.
Immediate
Latch
The system differential pressure for the respective circuit was below
35 Psid for more than 2000 Psid-sec with either a 1 minute (single
cprsr circuit) or 2.5 minute (manifolded cprsr circuit) ignore time from
the start of the circuit.
Immediate
Latch
Same as Low Differential Refrigerant Pressure - Circuit 1
Info
NonLatch
The liquid level sensor is seen to be at or near its low end of range for
80 contiguous minutes while the compressor is running. Design: 20%
or less of bit count corresponding to -21.2 mm or less liquid
level for 80 minutes)
Info
NonLatch
Same as Low Evaporator Liquid Level - Circuit 1
Immediate
Latch
a. The inferred Saturated Evap Refrigerant Temperature (calculated
from suction pressure transducer(s)) dropped below the Low
Refrigerant Temperature Cutout Setpoint for 120°F-sec (8°F-sec max
rate) while the circuit was running after the ignore period had expired.
The integral is held at zero for the ignore time (which is a function of
outdoor air temp) following the circuit startup and the integral will be
limited to never trip in less than 15 seconds, i.e. the error term shall
be clamped to 8°F The minimum LRTC setpoint is -5°F (18.7 Psia) the
point at which oil separates from the refrigerant. b. During the timeout
of the trip integral, the unload solenoid(s) of the running compressors
on the circuit, shall be energized continuously. Normal load/unload
operation will be resumed if the trip integral is reset by return to temps
above the cutout setpoint.
Immediate
Latch
Same as Low Evaporator Refrigerant Temperature - Circuit 1
Special
NonLatch
Any of the evap sat temps fell below the water temp cutout setting
Mode
while the respective evap liquid level was greater than –21.2mm for
30 degree F seconds while Chiller is in the Stop mode, or in Auto
mode with no compressors running. Energize Evap Water pump Relay
until diagnostic auto resets, then return to normal evap pump control.
Automatic reset occurs when either the evap temp rises 2°F (1.1°C)
above the cutout setting or the liquid level falls below -21.2mm for 30
minutes
Special
NonLatch
Same as Low Evaporator Temp - Ckt 1: Unit Off
Mode
Immediate
Latch
The intermediate oil pressure transducer for this compressor was
out of the acceptable pressure range for 15 seconds, while the Delta
Pressure was greater than 35 Psid.: Acceptable range is 0.50 > (PC-
PI) / (PC-PE) for the first 2.5 minutes of operation, and 0.25 > (PC-PI)
/ (PC- PE) there after,
Criteria
Reset Level
Remote
Local
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Local
RTAC-SVX002A-EN