Trane R Series Installation Operation & Maintenance page 70

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

RTAC-SVX002A-EN
Controls Interface
Active Chilled Water Subscreen
The active chilled water setpoint is that setpoint to which the unit is currently
controlling. It is determined by the front panel, Tracer, or external setpoints, which
in turn may be subject to a form of chilled water reset.
The chilled water reset status area in
the right most column will display one of
the following messages
- Return
- Constant Return
- Outdoor
- None
The left column text "Front Panel",
"BAS", "External", and "Active Chilled
Water Setpoint" will always be present.
In the second column, "_ _ _ _" will be
shown if that option is not installed.
Pressing the "Back" button takes you
back to the chiller screen.
Active Current Limit Setpoint
The active current limit setpoint is
the setpoint that is currently in use,
displayed in % RLA. Touching the
double arrow to the left of the Active
Current Limit Setpoint will change
the display to the active current limit
setpoint subscreen.