Tab. VI-07 – Setpoint Options/Conditions Displayed
Option
Ice Building
Cprsr Pumpdown
1
EXV Ckt Open
(For Authorized Service Use
Only
)
2
Ckt Lockout
Ext. Chilled Water Setpoint. Enable/ Disable
Ext. Chilled Current Limit
Setpoint
Notes:
1 Pumpdown procedure are discussed in Maintenance section 10.
2 Used for liquid level control or to recover from pumpdown.
RTAC-SVX002A-EN
Controls Interface
The remote devices identified on the following setpoint screen are discussed in the
Electrical.
Installation section of this manual.
Condition(s)
Enable/Disable
If future is installed, operation can be initiated or stopped.
Avail
Pumpdown is allowed: only with unit in Stop or when circuit is locked out.
Not Avail
Pumpdown is not allowed because unit is operating or pumpdown has
been completed.
Pumpdown
State is displayed while pumpdown is in progress.
Avail
Indicates EXV is closed but can be opened manually since unit is in Stop
or cicuit is Lockout
Not Avail
EXV is closed but cannot be opened manually since unit is operating
Open
State is displayed when EXV is open. Unit will not start with EXV
manually set open, but will initiate valve closure first.
Locked Out
Circuit is locked out at Front Panel, other circuit may be available to run.
Not Locked Out
Circuit is not locked out and is available to run.
Allows unit to control setpoint; otherwise another loop controller in line
will control, as optionally wired.
Enable/ Disable
Allows unit to control setpoint; otherwise another loop controller in line
will control, as optionally wired.
Explanation