Trane R Series Installation Operation & Maintenance page 88

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Hex
Diagnostic Name and
Code
Source
199
Low Oil Flow – Compressor
1B
19A
Low Oil Flow – Compressor
2A
19B
Low Oil Flow – Compressor
B5
Low Suction Refrigerant
Pressure - Circuit 1
B6
Low Suction Refrigerant
Pressure - Circuit 2
B7
Low Suction Refrigerant
Pressure - Cprsr 1B
B8
Low Suction Refrigerant
Pressure - Cprsr 2B
BA
Motor Current Overload –
Compressor 1A
BB
Motor Current Overload –
Compressor 1B
BC
Motor Current Overload –
Compressor 2A
BD
Motor Current Overload –
Compressor 2B
1AD
MP Application Memory CRC
Error
6A1
MP: Could not Store Starts
and Hours
5FF
MP: Invalid Configuration
6A2
MP: Non-Volatile Block Test
Error
69C
MP: Non-Volatile Memory
Reformat
D9
MP: Reset Has Occurred
1E1
Oil Flow Fault – Compressor
1A
1E2
Oil Flow Fault – Compressor
1B
5A0
Oil Flow Fault – Compressor
2A
5A1
Oil Flow Fault – Compressor
2B
1E6
Oil Temperature Sensor –
Cprsr 1B
1E8
Oil Temperature Sensor –
Cprsr 2B
1E6
Oil Temperature Sensor –
Cprsr 1A
1E8
Oil Temperature Sensor –
Cprsr 2B
RTAC-SVX002A-EN
Diagnostics
Severity
Persistence
Immediate
Latch
Same as Low Oil Flow - Compressor 1A
Immediate
Latch
Same as Low Oil Flow - Compressor 1A
Immediate
Latch
Same as Low Oil Flow - Compressor 1A
2B
Immediate
Latch
a. The Suction Refrigerant Pressure (or either of the compressor
suction pressures) dropped below 10 Psia just prior to compressor
start (after EXV preposition). b. The pressure fell below 16 Psia while
running after the ignore time had expired, or fell below 10 Psia (or 5
Psia in software prior to Oct'02) before the ignore time had expired.
The ignore time is function of outdoor air temperature. Note: Part b. is
identical to Low Evaporator Refrigerant Temperature diagnostic except
for the trip integral and trip point settings.
Immediate
Latch
Same as Low Suction Refrigerant Pressure - Circuit 1
Immediate
Latch
Same as Low Suction Refrigerant Pressure - Circuit 1
Immediate
Latch
Same as Low Suction Refrigerant Pressure - Circuit 1
Immediate
Latch
Compressor current exceeded overload time vs. trip characteristic.
For A/C products Must trip = 140% RLA, Must hold=125%, nominal
trip 132.5% in 30 seconds
Immediate
Latch
Same as Motor Current Overload - Compressor 1A
Immediate
Latch
Same as Motor Current Overload - Compressor 1A
Immediate
Latch
Same as Motor Current Overload - Compressor 1A
Immediate
Latch
Memory error criteria TBD
Info
Latch
MP has determined there was an error with the previous power down
store. Starts and Hours may have been lost for the last 24 hours.
Immediate
Latch
MP has an invalid configuration based on the current software
installed
Info
Latch
MP has determined there was an error with a block in the Non-Volatile
memory. Check settings.
Info
Latch
MP has determined there was an error in a sector of the Non-Volatile
memory and it was reformatted. Check settings.
Info
NonLatch
The main processor has successfully come out of a reset and built
its application. A reset may have been due to a power up, installing
new software or configuration. This diagnostic is immediately and
automatically cleared and thus can only be seen in the Historic
Diagnostic List in TechView
Immediate
Latch
The Intermediate Oil Pressure Transducer for this cprsr is reading a
pressure either above its respective circuit's Condenser Pressure by
15 Psia or more, , or below its respective Suction Pressure 10 Psia or
more for 30 seconds continuously.
Immediate
Latch
Same as Oil Flow Fault - Compressor 1A
Immediate
Latch
Same as Oil Flow Fault - Compressor 1A
Immediate
Latch
Same as Oil Flow Fault - Compressor 1A
Normal
Latch
Bad Sensor or LLID
Normal
Latch
Bad Sensor or LLID
Normal
Latch
Bad Sensor or LLID
Normal
Latch
Bad Sensor or LLID
Criteria
Reset Level
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Remote
Remote
Remote
Remote
Remote
Remote
Local
Local
Local
Local
Remote
Remote
Remote
Remote
88