Trane R Series Installation Operation & Maintenance page 91

Air-cooled helical rotary liquid chillers
Table of Contents

Advertisement

Hex
Diagnostic Name and
Code
Source
1ED
Starter Fault Type II –
Compressor 1A
1EE
Starter Fault Type II –
Compressor 1B
1EF
Starter Fault Type II –
Compressor 2A
1F0
Starter Fault Type II –
Compressor 2B
1F1
Starter Fault Type III –
Compressor 1A
1F2
Starter Fault Type III –
Compressor 1B
1F3
Starter Fault Type III –
Compressor 2A
1F4
Starter Fault Type III –
Compressor 2B
5C7
Starter Module Memory Error
Type 1 - Starter 2A
5C8
Starter Module Memory Error
Type 1 - Starter 2B
5C5
Starter Module Memory Error
Type 1Starter 1A
5C6
Starter Module Memory Error
Type 1-Starter 1B
5C9
Starter Module Memory Error
Type 2 - Starter 1A
5CA
Starter Module Memory Error
Type 2 - Starter 1B
5CB
Starter Module Memory Error
Type 2 - Starter 2A
5CC
Starter Module Memory Error
Type 2 - Starter 2B
6B1
Starter Panel High
Temperature Limit – Panel 1,
Cprsr 1B
6B0
Starter Panel High
Temperature Limit – Panel 1,
Cprsr 2A
6B2
Starter Panel High
Temperature Limit – Panel 2,
Cprsr 2B
5BA
Suction Refrigerant Pressure
Transducer – Circuit 1,
Compressor 1A
5BB
Suction Refrigerant Pressure
Transducer – Circuit 1,
Compressor 1B
5BC
Suction Refrigerant Pressure
Transducer - Circuit 2,
Compressor 2A
5BD
Suction Refrigerant Pressure
Transducer - Circuit 2,
Compressor 2B
91
Diagnostics
Severity
Persistence
Immediate
Latch
a. This is a specific starter test where the Shorting Contactor (1K3) is
individually energized and a check is made to ensure that there are
no currents detected by the CT's. If current is detected when only S is
energized at Start, then 1M is shorted. b. This test in a. above applies
to all forms of starters (Note: It is understood that many starters do not
connect to the Shorting Contactor.).
Immediate
Latch
Same as Starter Fault Type II - Compressor 1A
Immediate
Latch
Same as Starter Fault Type II - Compressor 1A
Immediate
Latch
Same as Starter Fault Type II - Compressor 1A
Immediate
Latch
As part of the normal start sequence to apply power to the compressor,
the Shorting Contactor (1K3) and then the Main Contactor (1 K1) were
energized. 1.6 seconds later there were no currents detected by the
CT's for the last 1.2 Seconds on all three phases. The test above
applies to all forms of starters except Adaptive Frequency Drives.
Immediate
Latch
Same as Starter Fault Type III - Compressor 1A
Immediate
Latch
Same as Starter Fault Type III - Compressor 1A
Immediate
Latch
Same as Starter Fault Type III - Compressor 1A
Info
Latch
Checksum on RAM copy of the Starter LLID configuration failed.
Configuration recalled from EEPROM.
Info
Latch
Same as Starter Module Memory Error Type 1 - Starter 2A
Info
Latch
Same as Starter Module Memory Error Type 1 - Starter 2A
Info
Latch
Same as Starter Module Memory Error Type 1 - Starter 2A
Immediate
Latch
Same as Starter Module Memory Error Type 1 - Starter 2A
Immediate
Latch
Same as Starter Module Memory Error Type 1 - Starter 2A
Immediate
Latch
Same as Starter Module Memory Error Type 1 - Starter 2A
Immediate
Latch
Same as Starter Module Memory Error Type 1 - Starter 2A
Special
NonLatch
Starter Panel High Limit Thermostat (170°F) trip was detected.
Mode
Note: Other diagnostics that may occur as an expected consequence
of the Panel High Temp Limit trip will be suppressed from annunciation.
These include Phase Loss, Power Loss, and Transition Complete
Input Open for Cprsr 1B
Special
NonLatch
Same as Starter Panel High Temperature Limit - Panel 1, Cprsr 1B
Mode
Special
NonLatch
Same as Starter Panel High Temperature Limit - Panel 1, Cprsr 1B
Model
Immediate
Latch
Bad Sensor or LLID Circuit target if no isolation valves, Compressor
target if isolation valves. Design Note: In the case of manifolded
compressors w/o isolation valves, the occurrence of this diagnostic
will also generate a comm loss with the nonexistent Suction Press
Cprsr 1B in order to accomplish circuit shutdown.
Immediate
Latch
Same as Suction Refrigerant Pressure Transducer - Circuit 1,
Compressor 1A
Immediate
Latch
Same as Suction Refrigerant Pressure Transducer - Circuit 1,
Compressor 1A
Immediate
Latch
Same as Suction Refrigerant Pressure Transducer - Circuit 1,
Compressor 1A
Criteria
Reset Level
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Local
Remote
Remote
Remote
Remote
RTAC-SVX002A-EN