Direction Of Rotation At Mechanical Position Indicator: Check; Limit Switching: Check - AUMA SQ Series Operation Instructions Manual

Part-turn actuators
Table of Contents

Advertisement

Commissioning (basic settings)
9.5.1.

Direction of rotation at mechanical position indicator: check

Information
9.5.2.

Limit switching: check

58
SQ 05.2
SQ 14.2 / SQR 05.2
Valve damage due to incorrect direction of rotation!
If the direction of rotation is wrong, switch off immediately (press STOP).
Eliminate cause, i.e. correct phase sequence for cable set wall bracket.
Repeat test run.
Switch off before reaching the end position.
1.
Move actuator manually to intermediate position or to sufficient distance from
end position.
2.
Switch on actuator in direction CLOSE and observe the direction of rotation on
the mechanical position indication:
For self-adjusting mechanical position indication:
The direction of rotation is correct if the actuator operates in direction
CLOSE and arrow
Figure 60: Direction of rotation
For mechanical position indication via indicator mark: (not self-adjust-
ing)
The direction of rotation is correct if the actuator operation in direction
CLOSE and the symbols ( / ) turn counterclockwise:
Figure 61: Direction of rotation
1.
Set selector switch to position Local control (LOCAL).
SQR 14.2 Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Profinet
turns clockwise in direction CLOSE (symbol
(for "clockwise closing" version")
/
(for "clockwise closing version")
).

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents