Indication Lights Of Local Controls; Mechanical Position Indication (Self-Adjusting) - AUMA SQ Series Operation Instructions Manual

Part-turn actuators
Table of Contents

Advertisement

SQ 05.2
SQ 14.2 / SQR 05.2
AC 01.2 Non-Intrusive Profinet
7.3.

Indication lights of local controls

7.4.

Mechanical position indication (self-adjusting)

SQR 14.2 Control unit: electronic (MWG)
Figure 55: Arrangement and signification of indication lights
[1]
Marking with symbols (standard)
[2]
Marking with figures 1
End position CLOSED reached (blinking: operation in direction CLOSE)
1
2 Tc Torque fault CLOSE
Motor protection tripped
3
4 To Torque fault OPEN
End position OPEN reached (blinking: operation in direction OPEN)
5
Bluetooth connection
6
Modify indication light assignment (indications)
Different indications can be assigned to LEDs 1
Device configuration M0053
Local controls M0159
Indication light 1 (left) M0093
Indication light 2 M0094
Indication light 3 M0095
Indication light 4 M0096
Indicat. light 5 (right) M0097
Signal interm. pos. M0167
Defaut values (Europe):
Indication light 1 (left) = End p. CLOSED, blink
Indication light 2 = Torque fault CLOSE
Indication light 3 = Thermal fault
Indication light 4 = Torque fault OPEN
Indicat. light 5 (right) = End p. OPEN, blink
Signal interm. pos. = OPEN/CLOSED = Off
Further setting values:
Refer to Manual (Operation and setting).
Figure 56: Mechanical position indicator
[1]
End position OPEN reached
[2]
End position CLOSED reached
6 (option)
5.
Indications
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents