Discharge Current Range:
Discharge Voltage Range:
Sampling Interval:
Data Transfer:
Operating Environment:
Power Requirements:
Find Quality Products Online at:
Standard DAC: 1.2V
Cell Voltage:
configurations available upon request
Single Load: 12 – 600A / Parallel Load: Up to 1200A
Range: 10 – 576V (Max) / Voltage Steps: 12V, 24V, 36V, 48V, 80V, 125V, 240V,
380V, 480V
Accuracy:
Discharge Current: 1% / Voltage: 0.5% – 0.8%
Resolution:
Discharge Current: 0.1 A or 0.5% / Voltage: 0.001 V
5 seconds – 1 minute
USB, Wireless (466 MHz)
Display:
Backlit LCD
0 – 40 °C (32 – 104 °F)
110/220 VAC 50/60 Hz / DC (from connected batteries)
Small: 400 x 177 x 288 mm (15.7 x 7 x 11.3 in)
Medium: 520 x 202 x 355 mm (20.5 x 8 x 14 in)
Dimensions:
Large: 555 x 225 x 435 mm (22.5 x 8.9 x 17.2 in)
X-Large: 603 x 400 x 740 mm (23.7 x 15.7 x 29 in)
XX-Large: 762 x 406 x 737 mm (30 x 16 x 29 in)
Small: 11 kg (24 lbs)
Weight:
Medium: 16 kg (36 lbs)
Large: 21 kg (47 lbs)
X-Large: 42 kg (93 lbs)
XX-Large: 55 kg (122 lbs)
GlobalTestSupply
www.
Technical Specifications
, 2V, 6V, 12V / Optional: Custom DAC