Time and Date Setting

Setting the system time and date correctly should be done before any discharge tests are
performed.
To set system time:
1. Select [Syst time] under the [System manage] menu
2. Use the up/down arrow keys to change number orientation
3. Use the left/right arrow keys to change number values
4. Press the ENT button to save the time/date setting

Parameter Management

Parameter management is used for various calibration and parameter settings.
Zero Calibration
To ensure measurement accuracy, zero calibration should be performed when the load bank
was unable to collect discharge voltage and current in normal operation.
To perform zero calibration:
1. Disconnect all measurement cables from the load bank and batteries
2. Select [Zero calib] under the [Param manage] menu
3. Press the ENT button to start calibration
Find Quality Products Online at:
Time setting
08/30/2016
12:30:00
Param manage
Zero calib
Measure calib
Mainboard Para
Parameter Management Menu