Cut-off Parameters for Discharge Auto-stop
There are four user defined parameters for setting the discharge auto-stop. If any of these
parameters are met the discharge test will end.
Use the left/right arrow keys to adjust the following values:
[Tot end U]: Indicates the total low-voltage cut-off for the battery string/system
[Cell end U]: Indicates the low-voltage cut-off of individual battery cells
[DIS C]: Indicates the capacity removed cut-off of the battery string
[DIS Time]: Indicates the time duration of the discharge test
Common Voltage Cutoff Values
Voltage value multiplied by (0.9)
1.2V = 1.08V
2V = 1.8V
6V = 5.4V
12V = 10.8V
After setting the cut-off parameters, press the down arrow key to progress to the next screen.
First Cell Polarity
The First Cell Polarity setting is used for DAC communication only. It is used to indicate which
end of the battery string, positive or negative, you have labeled as cell #1. Regardless of the
how the battery string is labeled DAC#1 always needs to be connected to the negative end of
the string.
When to use negative setting:
If the first battery in the string starts at the negative post, then DAC#1 will be connected to this
battery and the setting will be left as negative. When the test starts DAC#1 will correctly display
the first battery of the string as Battery #1.
Find Quality Products Online at:
Tot end U: 43 V
Cell end U: 10.80V
DIS C: 0000 Ah
DIS Time: 10H 00M
Parameters for Discharge Auto-Stop
(Reference only, verify with your battery's
GlobalTestSupply
www.
SLB-Series User Manual
manufacturer):
.com