Connection of antenna (Optional)
Screw the antenna into the socket on the top of the load bank. Bend the antenna down at
the hinge to reduce the chance of cables becoming caught.
Power supply
When power supply is from AC, connect the load bank to an appropriate AC power source
with the AC power cord. Turn the power switch at the back of load bank to AC 220 (or
110V mains). For special order DC models power supply is from batteries. In that case,
power will be supplied via the two load cables.
Breakers
If your unit is equipped with breakers, flip them into the ON position after powering the unit
on, prior to discharging.
Current clamp (Optional)
The following 3 auxiliary functions can make use of the current clamp:
External discharge:
Using the load bank during an external discharge. In this scenario the SLB-Series unit
functions to display the voltage and current values of the external load being applied to the
battery system.
Assistant discharge:
An assistant discharge is a function where the SLB supports either another SLB or any
other load bank. This function is useful if you already have an existing load bank and
would like to increase your discharge amps.
Charge monitor:
The purpose of the charge monitor is for viewing the status of the battery bank on float,
and recording the recovery of the battery system after a discharge event. To fully utilize
this function, both the DAC & CT packages should be purchased.

DAC Connection

The DAC (Data Acquisition Case) is an optional, but fundamental accessory for the Eagle Eye
SLB-Series. DACs are used for wireless data logging of each cells voltage in virtual real time. This
allows the load bank to capture each individual cells performance throughout the load test to help
isolate failed and weak cells. Using the DAC package also allows the user the added safety by
being able to utilize the low cell voltage feature of the SLB. When using this feature the user can
set a low cell voltage value, where in the event that any cell drops below this cutoff the load test
immediately stops for further investigation.