When to use positive setting:
If the first battery in the string starts at the positive post, then DAC#1 will be connected to the
last battery of the string and the setting will be set to positive. When the test starts DAC#1 will
display the last battery of the string correctly as the last battery and not the first.
If this setting is incorrect, the voltage readings of the cells will be reversed.

Starting a Discharge Test

When all of the discharge settings are set the discharge test can begin. When starting the test, a
60 second countdown can be enabled (system settings). Several events can occur during this
time:
If using the DataView Management Software the system information starts to populate.
If the total system or cell voltage is lower than the cutoff threshold, the test will not start.
If there is not enough memory on the unit to record another test, a memory error will
appear.
Using the arrow keys up/down it is also possible to view individual cell voltages. (DAC only)
Find Quality Products Online at:
DIS prepare, wait 55S
DIS C:
0.0Ah
U: 0.0V
I: 0.0A
Min cell:001# 2.001V
Discharge Countdown
001#2.001V 001#2.001V
001#2.001V 001#2.001V
001#2.001V 001#2.001V
001#2.001V 001#2.001V
Display of Cell Voltages