Discharge Testing

The following section covers steps for performing a discharge test. For an additional tutorial of
the SLB-Series menu, please visit our tutorial video
Battery String Discharge
Using the keypad and LCD display, press the arrow keys up/down to highlight [Discharge] and
press ENT to open the discharge test parameter screen.
Discharge Test Parameters
There are four system parameters to set for a discharge test. These settings vary slightly
depending on whether or not the test will include the use of DACs.
Use the left/right arrow keys to adjust the following values:
[Strg type]: Refers to the total voltage of the battery string/system
[Cell type]: Refers to the nominal cell voltage
[Cell No.]: Refers to the number of cells in the battery string,
value to "0"
[DIS I]: Refers to the working current to be applied to the system
After setting the discharge parameters, press the down arrow key to progress to the next
screen.
Find Quality Products Online at:
Battery DIS
DIS test
Continued DIS
Paral load
Discharge Menu
Strg type: 48V
Cell type: 12V
Cell No.: 4
DIS I: 000.0 A
Discharge Parameters
GlobalTestSupply
www.
SLB-Series User Manual
SLB Menu Walkthrough
Cell
if not using DAC set this