Slb Disconnection Workflow; Data Management - Eagle Eye SLB Series User Manual

Smart dc load banks
Table of Contents

Advertisement

4. Press ENT to begin monitoring the charge

SLB Disconnection Workflow

NOTE:
When a discharge test has completed, it is recommended that the SLB-Series unit be
left on to cool for 10 minutes. Immediately powering off the unit will not allow the fans to properly
cool down the internal components prior to storage.
Follow the steps below for proper take down of the SLB-Series test setup:
1. Flip the circuit breaker to the OFF position
2. Power off the unit
3. Disconnect power cord from load bank
4. Disconnect load cables from the batteries
5. Disconnect load cables from the load bank
6. Disconnect the voltage cable first from the battery and then from the load bank
7. Remove current clamp or serial cables if applicable
8. Disconnect DAC
9. Disconnect antenna

Data Management

All test data is saved to internal memory on the unit. This data can be directly viewed on the
screen or transferred to a USB drive and viewed in the Dataview software.
To view test data:
1. Select [Data] in the main menu
2. Select [View Data] and then select [DIS data] to display all of the test dates
3. Select a date, press ENT and then select [View] to display test data
Find Quality Products Online at:
Clamp
Tot warn U: 57 V
Cell warn U: 2.40 V
1# cell polar: -
Monitor Parameters
2012-06-25
2012-07-25
2012-08-25
2012-09-25
Test Dates
GlobalTestSupply
www.
type:025A/V
2012-06-25
2012-07-25
2012-08-25
WriteToUSB
2012-09-25
Delete
View Test Data
.com
SLB-Series User Manual
View
sales@GlobalTestSupply.com
35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents